ACS CONTROL SYSTEM Flow Transmitter FLUXICONT FU4

Add to Wishlist
Add to Wishlist

Flow switch and transmitter for basic industrial, sanitary, and aseptic applications.

Applications for hygiene.

♦ Compact design.

♦ Speed of response.

Description

ACS CONTROL SYSTEM Flow Transmitter FLUXICONT FU4

FU4SK is suitable for general applications in

  • Machinery and plant engineering
  • Air-conditioning and refrigeration plant engineering
  • Hydraulic and pneumatic systems
  • Process industry
  • Environmental technology

FU4LK is suitable for general applications in

  • Food and beverage industry
  • Pharmaceutical industry
  • Biotechnology
  • Sterile process engineering

FU4LK is an electronic flow and temperature switch for controlling, observing, and recording liquid flow and temperature over time.

wide range of applications, including those with severe measuring requirements, are made possible by the great variety of versions of process connections and electrical kinds.

The device can be used for wide range of applications due to its excellent precision and digital adjustment via RS485 Modbus®-RTU or IO-Link®. The device is made into a very high-quality product by its strong design and excellent workmanship, which makes it resistant  to even the harshest environmental circumstances, such as the coldest temperatures when used outdoors, extreme shock and vibration stress, or abrasive media.

 

material test certificate in accordance with EN10204 3.1, factory certification for drinkable water or food compatibility, factory calibration with calibration certificate, and customer-specific configuration or preset are additionally optionally available.

TECHNICAL DATA:-
Measuring range
Measuring principle Calorimetric flow measurement
Nominal measuring range 3…300cm/s
Output type V – RS485 Modbus®-RTU
Interface RS485, bidirectional
Modbus®-RTU
9600 Baud (4800…38400 Baud)
Time behavior Flow: T90 ≤ 6s / ton ≤ 10s
Temperature: T90 ≤ 4s / ton ≤ 2s
Output type L – IO-Link®
Interface IO-Link® V1.1
Com2 (38400 Baud)
Analogue output 0…20mA 0…20,5mA
≤ 0,05mA
≤ 22mA
dI ≤ 1µA
Analogue output 4…20mA 3,8mA…20,5mA
≥ 3,6mA
≤ 22mA
dI ≤ 1µA
Switch output 2xPP (Push-Pull), switch to +L/-L
Output Uout ≤ 0,2V ≥ Us – 2V
Iout = 0mA…200mA
current limited ≤ 450mA
short circuit protected
Time behavior Flow: T90 ≤ 6s / ton ≤ 10s
Temperature: T90 ≤ 4s / ton ≤ 2s
Auxiliary power
Supply voltage
(polarity protected)
Type V: 6V…35 V DC
Type L (without IO-Link®): 9V…35 V DC
Type L (with IO-Link®): 18V…30 V DC
Measuring accuracy
Accuracy Flow ≤ ±5% Measuring end value (5…100cm/s) (-20°C…+85°C)
≤ ±10% Measuring end value (100…175cm/s) (-20°C…+85°C)
Accuracy Temperature ≤ ±1,5K (≥ 20cm/s)
Long term drift Flow: ≤ ±10% of measuring value / year (-20°C…+85°C)
Temperature deviation Flow: ≤ ±0,4cm/s /K (-20°C…+85°C)
Environmental conditions
Environmental temperature -20°C…+100°C
Process temperature -20°C…+110°C (+140°C/1h)
Process pressure ≤ +40bar
Protection class IP69K/IP67 (EN/IEC 60529)