ACS HYDROCONT HP4 LEVEL SENSOR
Hydrostatic level measurement using a level sensor with a 22mm diameter and a capacitive ceramic measuring cell
with an RS485 Modbus-RTU output signal.
♦ Reliable and efficient ceramic cell.
♦ Possible integrated temperature measurement.
♦ Low consumption of energy.
Description
HYDROCONT HP4
LEVEL SENSOR
The Hydrocont HP4 device is an electronic sensor for continuous monitoring, control and measurement of filling level and temperature. The high precision and digital setting of RS485 Modbus®-RTU make the Hydrocont HP4 suitable for a wide range of applications. Application form. The solid design and high performance make the device very good and unaffected by the worst conditions, such as the lowest temperatures, shock, vibration, or heavy discharge when used outdoors.
Tethered laser type marking ensures identity throughout the life of the device. Obviously, an option displays the name of the indicator resp. Label or customer support, TAG and laser marking. Linked to the LAB Silicone-free version, factory calibration with calibration certificate and customer-specific configuration resp. Optional presets are also available, such as EN10204 3.1 test data certificate or factory certification for drinking water connection. Customer-specific versions can be realized at short notice on request. special design or other process information.
Application:-
• Water and wastewater sector.
• Machinery and plant engineering.
• Air-conditioning and refrigeration plant engineering.
• Hydraulic and pneumatic systems.
• Process industry.
• Environmental technology.
Main features:-
• Measuring ranges from 100 mbar up to 10 bar.
• Robust ceramic front-flush diaphragm.
• Precise dry capacitive sensor.
• Highest accuracy to ≤ 0,05%.
• Integrated long-term stable temperature sensor.
• Process temperature range –20°C to +70°C.
• Electronic RS485 Modbus®-RTU.
• Integrated overvoltage protection.
Input Pressure | |
---|---|
Nom. pressure PN relative | 0 bar … +0,1 bar up to 0 bar … +10 bar |
Characteristic deviation | ≤ ±0,05% FSO ≤ ±0,1% FSO ≤ ±0,2% FSO |
Temperature deviation | Tk Zero ≤ ±0,015% FSO/K Tk Zero ≤ ±0,75% FSO Tk Span ≤ ±0,015% FSO/K Tk Span ≤ ±0,5% FSO (at ≥ 0,4 bar) Tk Span ≤ ±0,8% FSO (at < 0,4 bar) |
Time behavior | T90 ≤ 2ms (td = 0s) |
---|
Input Temperature | |
---|---|
Sensor type | Pt1000 Class A |
Characteristic deviation | ≤ ±0,1K + 0,002 x [dt (25°C)] |
Time behavior | T90 ≤ 4s |
Output RS485 Modbus®-RTU | |
---|---|
Interface | RS485, bidirectional Modbus®-RTU 9600 Baud (4800…38400 Baud) |
Time behavior | ton ≤ 250ms (td = 0s) |
Auxiliary power supply | |
---|---|
y voltage Us (polarity protected) |
6 V…35 V DC |
Overvoltage protection | |
---|---|
Coarse protection | 75 V / 10kA – wave 8/20µs all lines to PE |
Fine protection | 36V all lines to -L |
Environmental conditions | |
---|---|
Environmental temperature | -20°C…+70°C |
Protection class | IP68 (EN/IEC 60529) |
Materials (Process wetted) |
Ceramic Al2O3 CrNi-Steel FPM EPDM PE PUR |