ACS CONTROL SYSTEM Flow Transmitter FLUXICONT FU4
Flow switch and transmitter for basic industrial, sanitary, and aseptic applications.
♦ Applications for hygiene.
♦ Compact design.
♦ Speed of response.
Description
ACS CONTROL SYSTEM Flow Transmitter FLUXICONT FU4
FU4SK is suitable for general applications in
- Machinery and plant engineering
- Air-conditioning and refrigeration plant engineering
- Hydraulic and pneumatic systems
- Process industry
- Environmental technology
FU4LK is suitable for general applications in
- Food and beverage industry
- Pharmaceutical industry
- Biotechnology
- Sterile process engineering
FU4LK is an electronic flow and temperature switch for controlling, observing, and recording liquid flow and temperature over time.
A wide range of applications, including those with severe measuring requirements, are made possible by the great variety of versions of process connections and electrical kinds.
The device can be used for a wide range of applications due to its excellent precision and digital adjustment via RS485 Modbus®-RTU or IO-Link®. The device is made into a very high-quality product by its strong design and excellent workmanship, which makes it resistant to even the harshest environmental circumstances, such as the coldest temperatures when used outdoors, extreme shock and vibration stress, or abrasive media.
A material test certificate in accordance with EN10204 3.1, a factory certification for drinkable water or food compatibility, a factory calibration with calibration certificate, and a customer-specific configuration or preset are additionally optionally available.
TECHNICAL DATA:-
Measuring range | |
---|---|
Measuring principle | Calorimetric flow measurement |
Nominal measuring range | 3…300cm/s |
Output type V – RS485 Modbus®-RTU | |
---|---|
Interface | RS485, bidirectional Modbus®-RTU 9600 Baud (4800…38400 Baud) |
Time behavior | Flow: T90 ≤ 6s / ton ≤ 10s Temperature: T90 ≤ 4s / ton ≤ 2s |
Output type L – IO-Link® | |
---|---|
Interface | IO-Link® V1.1 Com2 (38400 Baud) |
Analogue output 0…20mA | 0…20,5mA ≤ 0,05mA ≤ 22mA dI ≤ 1µA |
Analogue output 4…20mA | 3,8mA…20,5mA ≥ 3,6mA ≤ 22mA dI ≤ 1µA |
Switch output | 2xPP (Push-Pull), switch to +L/-L |
Output | Uout ≤ 0,2V ≥ Us – 2V Iout = 0mA…200mA current limited ≤ 450mA short circuit protected |
Time behavior | Flow: T90 ≤ 6s / ton ≤ 10s Temperature: T90 ≤ 4s / ton ≤ 2s |
Auxiliary power | |
---|---|
Supply voltage (polarity protected) |
Type V: 6V…35 V DC Type L (without IO-Link®): 9V…35 V DC Type L (with IO-Link®): 18V…30 V DC |
Measuring accuracy | |
---|---|
Accuracy Flow | ≤ ±5% Measuring end value (5…100cm/s) (-20°C…+85°C) ≤ ±10% Measuring end value (100…175cm/s) (-20°C…+85°C) |
Accuracy Temperature | ≤ ±1,5K (≥ 20cm/s) |
Long term drift | Flow: ≤ ±10% of measuring value / year (-20°C…+85°C) |
Temperature deviation | Flow: ≤ ±0,4cm/s /K (-20°C…+85°C) |
Environmental conditions | |
---|---|
Environmental temperature | -20°C…+100°C |
Process temperature | -20°C…+110°C (+140°C/1h) |
Process pressure | ≤ +40bar |
Protection class | IP69K/IP67 (EN/IEC 60529) |