Siemens PLC CPU 226 6ES7216-2BD23-0XB0
Add to Wishlist
Add to Wishlist
SIMATIC S7-200, CPU 226 Compact unit, AC power supply 24 DI DC/16 DO relay 16/24 KB program./10 KB data, 2 PPI/user-programmable interface.
Description
Siemens PLC CPU 226 6ES7216-2BD23-0XB0
Siemens PLC CPU 226
DATA SHEET:-
Supply voltage | ||
Rated value (AC) | ||
● 120 V AC | Yes | |
● 230 V AC | Yes | |
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● permissible range, lower limit (DC) | 5 V | |
● permissible range, upper limit (DC) | 30 V | |
Load voltage L1 | ||
● Rated value (AC) | 100 V; 100 V AC to 230 V AC | |
● permissible range, lower limit (AC) | 5 V | |
● permissible range, upper limit (AC) | 250 V | |
● permissible frequency range, lower limit | 47 Hz | |
● permissible frequency range, upper limit | 63 Hz | |
Input current | ||
Inrush current, max. | 20 A; at 264 V | |
from supply voltage L1, max. | 320 mA; 40 to 160 mA (240 V); 80 to 320 mA (120 V); output current for expansion modules (5 V DC) 1 000 mA | |
Encoder supply | ||
24 V encoder supply | ||
● 24 V | Yes; Permissible range: 20.4V to 28.8V | |
● Short-circuit protection | Yes; electronic at 400 mA | |
● Output current, max. | 400 mA | |
Power loss | ||
Power loss, typ. | 17 W | |
Memory | ||
Number of memory modules (optional) | 1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files | |
Work memory | ||
● integrated (for program) | 24 kbyte; 16 KB with active run-time edit | |
● integrated (for data) | 10 kbyte | |
Backup | ||
● present | Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenancefree on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering | |
Battery | ||
Backup battery | ||
● Backup time, max. | 100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module | |
CPU processing times | ||
for bit operations, max. | 0.22 µs | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 256 | |
Retentivity | ||
— adjustable | Yes; via high-performance capacitor or battery | |
— lower limit | 1 | |
— upper limit | 256 | |
Counting range | ||
— lower limit | 0 | |
— upper limit | 32 767 | |
S7 times | ||
● Number | 256 | |
Retentivity | ||
— adjustable | Yes; via high-performance capacitor or battery | |
— upper limit | 64 | |
Time range | ||
— lower limit | 1 ms | |
— upper limit | 54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 t
54 min |
|
Data areas and their retentivity | ||
Flag | ||
● Size, max. | 32 byte | |
● Retentivity available | Yes; M 0.0 to M 31.7 | |
● of which retentive with battery | 0 to 255, via high-performance capacitor or battery, adjustable | |
● of which retentive without battery | 0 to 112 in EEPROM, adjustable | |
Hardware configuration | ||
Number of expansion units, max. | 7; Only expansion modules of the S7-22x series can be used. D
limited output current, the use of expansion modules may be lim |
|
connectable programming devices/PCs | SIMATIC PG/PC, standard PC | |
Expansion modules | ||
● Analog inputs/outputs, max. | 35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 | |
● Digital inputs/outputs, max. | 148; max. 128 inputs and 120 outputs (CPU+EM) | |
● AS-Interface inputs/outputs, max. | 62; AS-Interface A/B slaves (CP 243-2) | |
Digital inputs | ||
Number of digital inputs | 24 | |
Source/sink input | Yes; optionally, per group | |
Input voltage | ||
● Rated value (DC) | 24 V | |
● for signal “0” | 0 to 5 V | |
● for signal “1” | min. 15 V | |
Input current | ||
● for signal “1”, typ. | 2.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; all | |
— at “0” to “1”, min. | 0.2 ms | |
— at “0” to “1”, max. | 12.8 ms | |
for interrupt inputs | ||
— parameterizable | Yes; I 0.0 to I 0.3 | |
for technological functions | ||
— parameterizable | Yes; (E 0.0 to E 1.5) 30 kHz | |
Cable length | ||
● shielded, max. | 500 m; Standard input: 500 m, high-speed counters: 50 m | |
● unshielded, max. | 300 m; not for high-speed signals | |
Digital outputs | ||
Number of digital outputs | 16; Relays | |
Short-circuit protection | No; to be provided externally | |
Switching capacity of the outputs | ||
● with resistive load, max. | 2 A | |
● on lamp load, max. | 200 W; 30 W with DC, 200 W with AC | |