Siemens PLC CPU 226 6ES7216-2AD23-0XB0
SIMATIC S7-200, CPU 226 Compact unit, DC power supply 24 DI DC/16 DO DC, 16/24 KB program./10 KB data, 2 PPI/user-programmable interface.
Description
Siemens PLC CPU 226 6ES7216-2AD23-0XB0
Siemens PLC CPU 226
Data Sheet:-
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● permissible range, lower limit (DC) | 20.4 V | |
● permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
Inrush current, max. | 10 A; at 28.8 V | |
from supply voltage L+, max. | 1 050 mA; 150 mA to 1 050 mA output current for expansion modules (5 V DC)1 000 mA | |
Encoder supply | ||
24 V encoder supply | ||
● 24 V | Yes; permissible range: 15.4 to 28.8 V | |
● Short-circuit protection | Yes; electronic at 400 mA | |
● Output current, max. | 400 mA | |
Power loss | ||
Power loss, typ. | 11 W | |
Memory | ||
Number of memory modules (optional) | 1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files | |
Work memory | ||
● integrated (for program) | 24 kbyte; 16 KB with active run-time edit | |
● integrated (for data) | 10 kbyte | |
Backup | ||
● present | Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering | |
Battery | ||
Backup battery | ||
● Backup time, max. | 100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module | |
CPU processing times | ||
for bit operations, max. | 0.22 µs | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 256 | |
Retentivity | ||
— adjustable | Yes; via high-performance capacitor or battery | |
— lower limit | 1 | |
— upper limit | 256 | |
Counting range | ||
— lower limit | 0 | |
— upper limit | 32 767 | |
S7 times | ||
● Number | 256 | |
Retentivity | ||
— adjustable | Yes; via high-performance capacitor or battery | |
— upper limit | 64 | |
Time range | ||
— lower limit | 1 ms | |
— upper limit | 54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to
54 min |
|
Data areas and their retentivity | ||
Flag | ||
● Size, max. | 32 byte | |
● Retentivity available | Yes; M 0.0 to M 31.7 | |
● of which retentive with battery | 0 to 255, via high-performance capacitor or battery, adjustable | |
● of which retentive without battery | 0 to 112 in EEPROM, adjustable | |
Hardware configuration | ||
Number of expansion units, max. | 7; Only expansion modules of the S7-22x series can be used. Due to the
limited output current, the use of expansion modules may be limited. |
|
connectable programming devices/PCs | SIMATIC PG/PC, standard PC | |
Expansion modules | ||
● Analog inputs/outputs, max. | 35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM) | |
● Digital inputs/outputs, max. | 148; max. 128 inputs and 120 outputs (CPU+EM) | |
● AS-Interface inputs/outputs, max. | 62; AS-Interface A/B slaves (CP 243-2) | |
Digital inputs | ||
Number of digital inputs | 24 | |
Source/sink input | Yes; optionally, per group | |
Input voltage | ||
● Rated value (DC) | 24 V | |
● for signal “0” | 0 to 5 V | |
● for signal “1” | min. 15 V | |
Input current | ||
● for signal “1”, typ. | 2.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; all | |
— at “0” to “1”, min. | 0.2 ms | |
— at “0” to “1”, max. | 12.8 ms | |
for interrupt inputs | ||
— parameterizable | Yes; I 0.0 to I 0.3 | |
for technological functions | ||
— parameterizable | Yes; (E 0.0 to E 1.5) 30 kHz | |
Cable length | ||
● shielded, max. | 500 m; Standard input: 500 m, high-speed counters: 50 m | |
● unshielded, max. | 300 m; not for high-speed signals | |
Digital outputs | ||
Number of digital outputs | 16; Transistor | |
Short-circuit protection | No; to be provided externally | |
Limitation of inductive shutdown voltage to | 1 W | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.75 A | |
● on lamp load, max. | 5 W | |
Output voltage | ||
● for signal “1”, min. | 20 V DC | |
Output current | ||
● for signal “1” rated value | 750 mA | |
● for signal “0” residual current, max. | 10 µA | |
Output delay with resistive load | ||
● “0” to “1”, max. | 15 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 2 µs; of the pulse outputs,
max. (Q 0.0 to Q 0.1) 2 µs |
|
● “1” to “0”, max. | 130 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 10 µs; of the pulse
outputs, max. (Q 0.0 to Q 0.1) 10 µs |
|
Parallel switching of two outputs | ||
● for uprating | Yes | |
Switching frequency | ||
● of the pulse outputs, with resistive load, max. | 20 kHz; Q0.0 to Q0.1 | |
Total current of the outputs (per group) | ||
all mounting positions | ||
— up to 40 °C, max. | 6 A | |
horizontal installation | ||
— up to 55 °C, max. | 6 A | |
Relay outputs | ||
● Number of relay outputs | 0 | |
Cable length | ||
● shielded, max. | 500 m | |
● unshielded, max. | 150 m | |
Analog inputs | ||
Number of analog potentiometers | 2; Analog potentiometer; resolution 8 bit | |
Encoder | ||
Connectable encoders | ||
● 2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1 mA | |
1. Interface | ||
Interface type | Integrated RS 485 interface | |
Protocols | ||
● MPI | Yes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs,
OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s |
|
● PPI | Yes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-
200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s |
|
● serial data exchange | Yes; As freely programmable interface with interrupt facility for serial data
exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter |
|
MPI | ||
● Transmission rate, min. | 19.2 kbit/s | |
● Transmission rate, max. | 187.5 kbit/s | |
2. Interface | ||
Interface type | Integrated RS 485 interface | |
Protocols | ||
● MPI | Yes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs,
OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s |
|
● PPI | Yes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-
200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s |
|
● serial data exchange | Yes; As freely programmable interface with interrupt facility for serial data
exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter |
|
Integrated Functions | ||
Counter | ||
● Number of counters | 6; High-speed counters (30 kHz each), 32 bit (incl. sign), can be used as
up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc. |
|
● Counting frequency, max. | 30 kHz | |
Number of alarm inputs | 4; 4 rising edges and/or 4 falling edges | |
Number of pulse outputs | 2; High-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency
modulation option |
|
Limit frequency (pulse) | 20 kHz | |