SIEMENS SIMATIC S7-1500 Communication Module CM PTP RS422/485 BA
Add to Wishlist
Add to Wishlist
SIMATIC S7-1500, CM PTP RS422/485 BA Communication module for Serial connection RS422,RS485 Freeport, 3964 (R), USS, 19200 Kbit/s, 15-Pin D-sub socket.
Description
SIEMENS SIMATIC S7-1500 Communication Module
CM PTP RS422/485 BA
General information | ||
Product type designation | CM PtP RS 422 / 485 BA | |
Product function | ||
● I&M data | Yes; I&M 0 | |
● Fast startup | Yes | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated from version | V12 / V12 | |
● STEP 7 configurable/integrated from version | V5.5 SP2 with GSD file | |
● PROFIBUS from GSD version/GSD revision | – / – | |
● PROFINET from GSD version/GSD revision | V2.3 | |
Installation type/mounting | ||
Rail mounting | Yes; S7-1500 mounting rail | |
Supply voltage | ||
Design of the power supply | system power supply | |
Input current | ||
Current consumption (rated value) | 43 mA; From the backplane bus | |
Power | ||
Power available from the backplane bus | 0.65 W | |
Power loss | ||
Power loss, typ. | 0.6 W | |
Address area | ||
Address space per module | ||
● Inputs | 8 byte | |
Interface types | ||
RS 485 | ||
● Transmission rate, max. | 19.2 kbit/s | |
● Cable length, max. | 1 200 m | |
RS 422 | ||
● Transmission rate, max. | 19.2 kbit/s | |
● Cable length, max. | 1 200 m | |
● 4-wire full duplex connection | Yes | |
● 4-wire multipoint connection | No | |
Protocols | ||
Integrated protocols | ||
Freeport | ||
— Telegram length, max. | 1 kbyte | |
— Bits per character | 7 or 8 | |
— Number of stop bits | 1 or 2 bit | |
— Parity | None, even, odd, always 1, always 0, any | |
SIEMENS SIMATIC S7-1500 Communication Module
3964 (R) | ||
— Telegram length, max. | 1 kbyte | |
— Bits per character | 7 or 8 | |
— Number of stop bits | 1 or 2 bit | |
— Parity | None, even, odd, always 1, always 0, any | |
Telegram buffer | ||
● Buffer memory for telegrams | 2 kbyte | |
● Number of telegrams which can be buffered | 255 | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | No | |
Diagnoses | ||
● Wire-break | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; green LED | |
● ERROR LED | Yes; red LED | |
● Receive RxD | Yes; Yellow LED | |
● Transmit TxD | Yes; Yellow LED | |
Potential separation | ||
between backplane bus and interface | Yes | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | 0 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | 0 °C | |
● vertical installation, max. | 40 °C | |
Altitude during operation relating to sea level | ||
● Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200MP systemmanual | |
Decentralized operation | ||
to SIMATIC S7-300 | Yes | |
to SIMATIC S7-400 | Yes | |
to SIMATIC S7-1500 | Yes | |
to standard PROFINET controller | Yes | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 127 mm | |
Weights | ||
Weight, approx. | 0.22 kg | |