SIEMENS PLC CPU 224XP 6ES7214-2AD23-0XB0
SIMATIC S7-200, CPU 224XP Compact unit, DC power supply 14 DI DC/10 DO DC, 2 AI, 1 AO, 12/16 KB progr./10 KB data, 2 PPI/user-programmable interface.
Description
SIEMENS PLC CPU 224XP 6ES7214-2AD23-0XB0
SIEMENS PLC CPU 224XP
Data sheet:-
Supply voltage | |||
Rated value (DC) | |||
● 24 V DC | Yes | ||
Load voltage L+ | |||
● Rated value (DC) | 24 V | ||
● permissible range, lower limit (DC) | 20.4 V | ||
● permissible range, upper limit (DC) | 28.8 V | ||
Input current | |||
Inrush current, max. | 12 A; at 28.8 V | ||
from supply voltage L+, max. | 900 mA; 120 mA to 900 mA, output current for expansion modules (5 V DC)
660 mA |
||
Encoder supply | |||
24 V encoder supply | |||
● 24 V | Yes; permissible range: 15.4 to 28.8 V | ||
● Short-circuit protection | Yes; electronic at 280 mA | ||
● Output current, max. | 280 mA | ||
Power loss | |||
Power loss, typ. | 8 W | ||
Memory | |||
Number of memory modules (optional) | 1; pluggable memory module, content identical with integral EEPROM; can
additionally store recipes, data logs and other files |
||
Work memory | |||
● integrated (for program) | 16 kbyte; 12 KB with active run-time edit | ||
● integrated (for data) | 10 kbyte | ||
Backup | |||
● present | Yes; Program: Entire program maintenance-free on integral EEPROM,
programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenancefree on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering |
||
Battery | |||
Backup battery | |||
● Backup time, max. | 100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module | ||
CPU processing times | |||
for bit operations, max. | 0.22 µs | ||
Counters, timers and their retentivity | |||
S7 counter | |||
● Number | 256 | ||
— adjustable | Yes; via high-performance capacitor or battery | ||
— lower limit | 1 | ||
— upper limit | 256 | ||
Counting range | |||
— lower limit | 0 | ||
— upper limit | 32 767 | ||
S7 times | |||
● Number | 256 | ||
Retentivity | |||
— adjustable | Yes; via high-performance capacitor or battery | ||
— upper limit | 64 | ||
Time range | |||
— lower limit | 1 ms | ||
— upper limit | 54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to
54 min |
||
ata areas and their retentivity | |||
Flag | |||
● Size, max. | 32 byte | ||
● Retentivity available | Yes; M 0.0 to M 31.7 | ||
● of which retentive with battery | 0 to 255, via high-performance capacitor or battery, adjustable | ||
● of which retentive without battery | 0 to 112 in EEPROM, adjustable | ||
ardware configuration | |||
Number of expansion units, max. | 7; Only expansion modules of the S7-22x series can be used. Due to the
limited output current, the use of expansion modules may be limited. |
||
connectable programming devices/PCs | SIMATIC PG/PC, standard PC | ||
Expansion modules | |||
● Analog inputs/outputs, max. | 38; 2 onboard inputs and 1 output, also max. 28 inputs and 7 outputs (EM) or
max. 0 inputs and 14 outputs (EM) |
||
● Digital inputs/outputs, max. | 168; max. 94 inputs and 74 outputs (CPU + EM) | ||
● AS-Interface inputs/outputs, max. | 62; AS-Interface A/B slaves (CP 243-2) | ||
gital inputs | |||
Number of digital inputs | 14 | ||
Source/sink input | Yes; optionally, per group | ||
nput voltage | |||
● Rated value (DC) | 24 V | ||
● for signal “0” | 0V to 5V; 0V to 1V (I0.3 to I0.5) | ||
● for signal “1” | min. 15 V; min. 4 V (I 0.3 to I 0.5) | ||
nput current | |||
● for signal “1”, typ. | 2.5 mA; 8 mA for I0.3 to I0.5 | ||
nput delay (for rated value of input voltage) | |||
for standard inputs | |||
— parameterizable | Yes; all | ||
— at “0” to “1”, min. | 0.2 ms | ||
— at “0” to “1”, max. | 12.8 ms | ||
for interrupt inputs | |||
— parameterizable | Yes; I 0.0 to I 0.3 | ||
for technological functions | |||
— parameterizable | Yes; (E 0.0 to E 1.5) up to 200 kHz | ||
Cable length | |||
● shielded, max. | 500 m; Standard input: 500 m, high-speed counters: 50 m | ||
● unshielded, max. | 300 m; not for high-speed signals | ||
gital outputs | |||
Number of digital outputs | 10; Transistor | ||
Short-circuit protection | No; to be provided externally | ||
Limitation of inductive shutdown voltage to | 1 W | ||
Switching capacity of the outputs | |||
● with resistive load, max. | 0.75 A | ||
● on lamp load, max. | 5 W | ||
Output voltage | |||
● for signal “1”, min. | L+ (-0.4 V (5 V / 20.4 V for A 0.0 to A 0.4; 20.4 V A 0.5 to A1.1)) | ||
Output current | |||
● for signal “1” rated value | 750 mA | ||
● for signal “0” residual current, max. | 10 µA | ||
Output delay with resistive load | |||
● “0” to “1”, max. | 15 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 15 µs; of the pulse
outputs, max. (Q 0.0 to Q 0.1) 0.5 µs |
||
● “1” to “0”, max. | 130 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 130 µs; of the pulse
outputs, max. (Q 0.0 to Q 0.1) 1.5 µs |
||
Parallel switching of two outputs | |||
● for uprating | Yes | ||
Switching frequency | |||
● of the pulse outputs, with resistive load, max. | 100 kHz; Q0.0 to Q0.1 | ||
Total current of the outputs (per group) | |||
all mounting positions | |||
— up to 40 °C, max. | 3.75 A | ||
horizontal installation | |||
— up to 55 °C, max. | 3.75 A | ||
Relay outputs | |||
● Number of relay outputs | 0 | ||
Cable length | |||
● shielded, max. | 500 m | ||
● unshielded, max. | 150 m | ||
Analog inputs | |||
Number of analog potentiometers | Number of analog potentiometers | ||
Encoder | |||
Connectable encoders | |||
● 2-wire sensor | Yes | ||
— permissible quiescent current (2-wire sensor), max. | 1 mA | ||
1. Interface | |||
Interface type | Integrated RS 485 interface | ||
Protocols | |||
● MPI | Yes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs,
OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s |
||
● PPI | Yes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-
200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s |
||
● serial data exchange | Yes; As freely programmable interface with interrupt facility for serial data
exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter |
||
MPI | |||
● Transmission rate, min. | 19.2 kbit/s | ||
● Transmission rate, max. | 187.5 kbit/s | ||
2. Interface | |||
Interface type | Integrated RS 485 interface | ||
Protocols | |||
● MPI | Yes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs,
OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s |
||
● PPI | Yes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-
200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s |
||
● serial data exchange | Yes; As freely programmable interface with interrupt facility for serial data
exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter |
||
|
Integrated Functions | ||
Counter | |||
● Number of counters | 6; High-speed counters (2 to 200 kHz and 4 to 30 kHz), 32 bit (incl. sign), can
be used as up/down counters or for connecting incremental encoders with 2 pulse trains offset by 90° (max. 1 to 100 kHz and 3 to 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc. |
||
● Counting frequency, max. | 200 kHz | ||
Number of alarm inputs | 4; 4 rising edges and/or 4 falling edges | ||
Number of pulse outputs | 2; High-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency
modulation option |