SIEMENS Differential Pressure Sensor QBM2030

Add to Wishlist
Add to Wishlist

Pressure-linear characteristic with selectable pressure measuring range.

Operating voltage AC 24 V or DC 13.5…33 V.

Output signal DC 0…10 V.

Zero-point adjustment.

Simple and fast mounting thanks to integrated mounting brackets in the housing.

Maintenance free.

Calibrated and temperature-compensated measuring signal.

Supplied with tubing connection set.

Description

SIEMENS Differential Pressure Sensor QBM2030

Application:-

The differential pressure sensor acquires differential, over, and under the pressure of air and nonaggressive gases.

Fields of application-

Measuring the slightest differential pressures in ventilation and air conditioning ducts.

Check air flows.

Monitor filters and control fans.

SIEMENS Differential Pressure Sensor QBM2030

TECHNICAL DATA:-

Electrical interface-

Power supply safety y extra low voltage (SELV/PELV)
Operating voltage AC AC 24 V ±15 %, 50/60 Hz or DC 13.5…33 V
Power consumption <0.5 VA
Current draw <10 external
l supply line protection  

Fuse slow max. 10 A

or circuit breaker max. 13 ACharacteristic B, C, D according to EN 60898 power source with current limitation of max. 10 A

Output voltage DC 0…10 V
Burden (RLoad) >10 k
Output Not galvanically separated, 3-wire connection,

short-circuit proof, protected against reverse

polarity

Functional data-

Measuring range refer to “Type summary”
Sensing element Piezo-resistive (silicone membrane, ceramic bar)
Measuring accuracy at recommended mounting position and 20 °C ambient temperature (FS = Full Scale)
Total error <±3 % FS
TC zero point <±0.1 % FS/°C
TC sensitivity <±0.06 % FS/°
Reaction time 1 s
Tolerable overload on one side on P1on P2 5,000 Pa(10,000 Pa for types QBM2030-5, -30)400 Pa
Rupture pressure0…70 °Cat room temperature 1.5 × overload 2 × overload
Media Air and non-aggressive gases
Admissible medium temperature 0…70 °C

Connections-

Electrical connection
Screw terminals for max. 1.5 mm2 (wire or stranded wire)
Cable lead Cable gland entry Pg 11 (without cable strain relief)

Degree of protection-

Protection degree of housing at recommended installation IP42 according to EN 60529
Protection class III according to EN 60730-1

Environmental conditions-

Permissible ambient temperature
Operation 0…70 °C
Transport/storage -25…+70 °C
Permissible ambient humidity <90 % r.h. (without condensation)