PULS POWER SUPPLY CT5.121
DIN rail power supplies for 3-phase system 12 V, 8 A
♦ AC 380-480V Wide-range Input.
♦ Input Fuses Already Included.
♦ Requires only Two Legs of a 3-Phase System.
♦ Width only 40mm.
♦ Efficiency up to 85.8%.
♦ Input -Transient Blanking Circuit Included.
♦ Minimal Inrush Current Surge.
♦ Full Power Between -25°C and +60°C.
Description
PULS POWER SUPPLY CT5.121
CT-Series-3-PHASE, 12V, 8A, 96W.
The Dimension CT-Series are cost-optimized power supplies without compromising quality, reliability, and performance. The CT-Series is part of the DIMENSION power supply family. The most outstanding features of CT5.121 are the high efficiency, electronic inrush current limitation, active input transient filter and wide operational temperature range, small size, and other technological design concepts. The CT-Series includes all the essential basic functions. The CT5.121 utilizes only 2 legs of a 3-phase system which saves wiring and installation costs. Furthermore, this allows a smaller unit without compromising the size of the terminals. Due to the low power consumption, an unbalancing of the individual phases is not expected.
SHORT-FORM DATA-
Output voltage | DC 12V | Nominal |
Adjustment range | 12 – 15V | Factory setting 12.0V |
Output current | 8.0 – 6.4A | Up to +60°C ambient |
6.0 – 4.8A | At +70°C ambient | |
Derate linearly between +60°C and +70°C | ||
Input voltage AC | AC 380-480V | -15%/+20% |
Mains frequency | 50-60Hz | ±6% |
Input current AC | 0.64 / 0.56A | At 400 / 480Vac |
Power factor | 0.44 / 0.42 | At 400 / 480Vac |
AC Inrush current | 4 / 4Apk | At 400 / 480Vac |
Efficiency | 85.4 / 85.8% | At 400 / 480Vac |
Losses | 16.4 / 15.9W | At 400 / 480Vac |
Hold-up time | 43 / 63ms | At 400 / 480Vac |
Temperature range | -25°C to +70°C | |
Size (WxHxD) | 40x124x117mm | Without DIN rail |
Weight | 500g |
PULS POWER SUPPLY CT5.121
AC-INPUT
The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. Grounding of one phase is allowed except for UL508 applications.
AC input
AC input range
|
Nom.
|
AC 380-480V
323-576Va 576-700Vac
|
For maximal 1s (occasional)
|
||
Allowed voltage L or N to earth
|
Max.
|
500Vac
|
Continuous operation, according to IEC 62477-1
|
||
Input frequency
|
Nom.
|
50–60Hz
|
±6%
|
||
Turn-on voltage
|
Typ.
Typ. Typ. Typ.
|
270Vac
185Vac 215Vac 225Vac |
Load independent, steady-state value, see Fig. 3-1
At no load
|
Input current | Typ. | 0.64A | 0.56A | At 12V, 8A, see Fig. 3-3 |
Power factor | Typ. | 0.44 | 0.42 | At 12V, 8A, see Fig. 3-4 |
Start-up delay | Typ. | 75ms | 75ms | See Fig. 3-2 |
Rise time | Typ. | 50ms | 50ms | At 12V, 8A const. current load, 0mF load
capacitance, see Fig. 3-2 |
Typ. | 85ms | 85ms | At 12V, 8A const. current load, 8mF load
capacitance, see Fig. 3-2 |
|
Turn-on overshoot | Max. | 100mV | 100mV | See Fig. 3-2 |
OUTPUT:-
The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage.The device is designed to supply any kind of loads, including unlimited capacitive and inductive loads.The output is electronically protected against overload, no-load and short-circuits. In case of a protection event,audible noise may occur.
Output voltage | Nom. | 12V | |
Adjustment range | 12-15V | Guaranteed value | |
Max. | 16V | This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value which can be achieved. |
|
Factory setting output voltage | Typ. | 12.0V | ±0.2% at full load, cold unit |
Line regulation | Max. | 10mV | Between 323 and 576Vac input voltage change |
Load regulation | Max. | 100mV | Between 0 and 8A in “single use” mode, static value |
Ripple and noise voltage | Max. | 100mVpp | Bandwidth 20Hz to 20MHz, 50Ohm |
Output current | Nom. | 8.0A | At 12V and 60°C ambient temperature |
Nom. | 6.0A | At 12V and 70°C ambient temperature | |
Nom. | 6.4A | At 15V and 60°C ambient temperature | |
Nom. | 4.8A | At 15V and 70°C ambient temperature | |
Reduce output current linearly between +60°C and +70°C | |||
Overload behavior | Continuous current | See Fig. 6-1 | |
Overload/ short-circuit current | Max. | 15A | Continuous current, see Fig. 6-1 |
Output capacitance | Typ. | 5 200µF | Included inside the power supply |
Back-feeding loads | Max. | 25V | The unit is resistant and does not show
malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The absorbing energy can be calculated according to the built-in large sized output capacitor |