Autonics TNL Series-2-DOF PID Temperature Controllers
Temp Control, 1/4 DIN, Zone PID, RS485, 100-240VAC; Fixed Control, 4 Alarm, Current/SSR Drive Out1&2, 1 CT+3 Digital Input,
Description
Autonics TNL Series – 2-DOF PID Temperature Controllers
The TNL series has RS485 connection, DIN 96 (width) x 96 (height) mm dimensions, and 4 alarm outputs (with fixed control units) or 6 alarm outputs (with program control units). Choose from a number of input/output options and control output combinations (control outputs 1 and 2).
2-DOF PID Temperature Controllers (Program/Fixed Control)
With a high-speed sampling speed of 50 ms and measurement accuracy of 0.2%, the TN series temperature controllers provide high precision temperature control. For the best temperature control in a variety of applications, the temperature controllers include simultaneous heating and cooling control, group PID, zone PID control, and anti-reset windup capabilities.
Main Features:-
♦ Optimized 2-DOF PID algorithm for a range of control applications.
♦ High-speed sampling at 50 ms and display accuracy of 0.2%.
♦ Program control and fixed control models available
-
- Up to 10 patterns x 20 steps program setting (program control model)
- Timer function for preset operation (fixed control model)
♦Simultaneous heating and cooling, as well as automated and manual control.
♦ Group PID, Zone PID, and Anti Reset Windup are control functions (ARW).
♦ Monitoring of up to 10 events’ control status.
♦ Available RS485 connection output model.
- Communication protocols: Modbus RTU/ASCII, PLC ladder-less, Sync-Master
- Communication speed: up to 115,200bps
♦ Function of the heater burnout alert (CT input).
♦ Parameter setting via PC
-
- Comprehensive Device Management Software (DAQMaster) provided
- Communication converter connection with front loader port (TNH, TNL only)
♦ Setting shortcut keys with the front key button (U).
♦ With detachable terminal blocks, maintenance is simple.
Autonics TNL Series – 2-DOF PID Temperature Controllers
Data Sheet
Power supply | 100-240VAC~ 50/60Hz |
Power consumption | Max. 8VA |
Display method | 11 segment |
Sampling cycle | 50 / 100 / 250 ms (parameter) |
Option input_CT input | • 0.0-50.0 A (primary current measurement range) • CT ratio: 1/1 |
Option input_Digital inputs | • Contact – ON: ≤ 2 kΩ |
Control output_Current | DC 0 – 20 mA or DC 4 – 20 mA (parameter), Load resistance: ≤ 500 Ω |
Option output_Alarm | 250VAC~ 3A 1a |
Option output_Trans. | DC 4 – 20 mA (load resistance: ≤ 500 Ω, output accuracy: ±0.3% F.S.) |
Option output_Comm. | RS485 |
Control type_Type | ON/OFF, P, PI, PD, PID |
Control type_Multi SV | ≤ 4 SV |
Control type_Group PID | ≤ 8 group |
Control type_Zone PID | 4 zones |
Control type_ARW | 50 to 200 % |
Program control_Program | ≤ 10 patterns |
Program control_Step | ≤ 200 steps (1 pattern: ≤ 20 steps) |
Program control_Setting type | Time setting |
Hysteresis | • Thermocouple, RTD: 1 to 100 (0.1 to 100.0) ℃/℉ • Analog: 1 to 100 digit |
Dielectric strength | Between primary terminal and case: 3,000 VAC~ 50/60 Hz for 1 min |
Vibration | 0.75 mm amplitude at frequency of 5 to 55 Hzin each X, Y, Z direction for 2 hours |
Relay life cycle_Mechanical | • OUT1/2: ≥ 5,000,000 operations • AL1/2/3/4/5/6: ≥ 20,000,000 operations |
Relay life cycle_Electrical | • OUT1/2: ≥ 200,000 operations • AL1/2/3/4/5/6: ≥ 100,000 operations |
Insulation resistance | ≥ 100 MΩ (500 VDC megger) |
Insulation type | Double insulation or reinforced insulation (mark: , dielectric strength between the measuring input part and the power part: 3 kV) |
Noise immunity | ±2 kV square shaped noise by noise simulator (pulse width: 1 ㎲) R-phase, S-phase |
Memory Protection | ≈ 10 years (non-volatile semiconductor memory type) |
Ambient temperature | -10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation) |
Ambient humidity | 35 to 85%RH |
Protection structure | IP65 (Front panel, IEC standards) |
Loader port | Front side |
Accessories | Bracket |
Weight | 301 g |