ACS CONTROL SYSTEM ULTRASONIC FLOWMETER FLOWCONT UN
Add to Wishlist
Add to Wishlist
Ultrasonic flowmeter
✓ Suitable for use with both conductive and non-conductive liquids.
✓ Due to the seal-free sensor, there is high process safety.
✓ The measurement tube can move easily.
Description
ACS CONTROL SYSTEM ULTRASONIC FLOWMETER FLOWCONT UN
Ultrasonic flowmeter FLOWCONT UN
Compared to swimming with the current, swimming against it demands more physical strength. This is the basic tenet on which phase difference-based ultrasonic flow monitoring is based. Sending and receiving ultrasonic waves alternately between two sensors that are placed across from one another.
The supplied ultrasonic flowmeter signal is received in phase, or without phase difference, by both sensors when static mediums are employed. A phase shift occurs when flowing media are used. When measured against the current direction as opposed to in it, the phase shift is
different. The flow’s velocity and the phase difference are directly inversely proportional. Based on the flow’s velocity and the pipeline’s known diameter,
the flow volume is calculated.
FEATURES:-
🗹 conductive and non conductive liquid flow sensors.
🗹 No moving parts and small in size.
🗹 Process pressure up to 10 bar, process temperature up to 80 °C.
🗹 Due to the seal-free sensor design, there is high chemical resistance.
🗹 A sizable display with a membrane keypad and integrated tube detecting.
🗹 Variants that are simple to clean, hygienic, and CIP competent are available (they have EHEDG certification and FDA compliance).
TECHNICAL DATA:-
Power supply | 18V…30 V DC protected against polarity reversal short circuit and over load protected |
---|---|
Supply current | ≤ 180mA |
Measurement accuracy | ≤ 2% (from end value) |
Materials | |
---|---|
Housing (medium contact) |
PSU polysulfone (Ultrason S) |
Environmental conditions | |
---|---|
Ambient temperature | -20°C…+70°C |
Process temperatures | 0°C…+80°C |
Process pressure ranges | DN 10 / DN 15: ≤ +10bar DN 20 / DN 25: ≤ +6bar |
Protection class | IP67 |
Residual ripple | ≤ 5Vss |
---|---|
Initialization time | ≤ 5s |
Protection class | III |
Connection type | M12x1 / 5-pol. M12x1 / 8-pol. |
Impulse/Frequency output | 0kHz…10kHz pulse width ≤ 1s |
signal voltage | HIGH UV – 2V LoW ≤ 2V |
Output current | < 100mA |
Load | inductive: 1H capacitive: 100nF |
Response time | filter off: 100ms filter low: 300ms filter middle: 1s filter strong: 4,2s |
Output load | < 500Ohm |
Signal level | lower signal level: 3,8mA…4mA upper signal level: 20mA…20,5mA |