Siemens DIN Rail Power Supply Sitop -6EP1333-2BA20-5A

Add to Wishlist
Add to Wishlist

SITOP PSU100S/1AC/24VDC/5A
SITOP PSU100S 24 V/5 A Stabilized power supply input: 120/230 V AC, output: 24 V DC/5 A *Ex approval no longer available.

Description

Siemens DIN Rail Power Supply Sitop-6EP1333-2BA20-5A

DIN Rail Power Supply

Input
type of the power supply network 1-phase AC
supply voltage at AC
● initial value Automatic range selection
supply voltage
● 1 at AC rated value 120 V
● 2 at AC rated value 230 V
input voltage
● 1 at AC 85 … 132 V
● 2 at AC 170 … 264 V
design of input wide range input No
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
operating condition of the mains buffering at Vin = 93/187 V
buffering time for rated value of the output current in the event of power failure minimum 20 ms
operating condition of the mains buffering at Vin = 93/187 V
line frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
line frequency 47 … 63 Hz
input current
● at rated input voltage 120 V 2.34 A
● at rated input voltage 230 V 1.36 A
current limitation of inrush current at 25 °C maximum 40 A
I2t value maximum 1 A²·s
fuse protection type T 3,15 A/250 V (not accessible)
● in the feeder Recommended miniature circuit breaker: from 6 A characteristic C
Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 1 %
residual ripple
● maximum 150 mV
● typical 30 mV
voltage peak
● maximum 240 mV
● typical 140 mV
adjustable output voltage 22.8 … 28 V
product function output voltage adjustable Yes
type of output voltage setting via potentiometer
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”
behavior of the output voltage when switching on Overshoot of Vout < 3 %
response delay maximum 0.3 s
voltage increase time of the output voltage
● typical 15 ms
output current
● rated value 5 A
● rated range 0 … 6 A; 6 A up to +45°C; +60 … +70 °C: Derating 1.6%/K
supplied active power typical 144 W
short-term overload current
● on short-circuiting during the start-up typical 18 A
● at short-circuit during operation typical 18 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 800 ms
● at short-circuit during operation 800 ms
product feature
● bridging of equipment Yes
number of parallel-switched equipment resources for increasing

the power

2
Efficiency
efficiency in percent 88 %
power loss [W]
● at rated output voltage for rated value of the output

current typical

16 W
Closed-loop control
relative control precision of the output voltage with rapid

fluctuation of the input voltage by +/- 15% typical

0.3 %
relative control precision of the output voltage at load step of

resistive load 10/90/10 % typical

3 %
setting time
● load step 10 to 90% typical 1 ms
● load step 90 to 10% typical 1 ms
Protection and monitoring
design of the overvoltage protection protection against overvoltage in case of internal fault Vout < 33 V
response value current limitation 6 … 7.1 A
property of the output short-circuit proof Yes
design of short-circuit protection Constant current characteristic
enduring short circuit current RMS value
● typical 7.1 A
overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
display version for overload and short circuit
Safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.4 mA
protection class IP IP20
Approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus

(CSA C22.2 No. 60950-1, UL 60950-1)

● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus

(CSA C22.2 No. 60950-1, UL 60950-1)