Siemens Analog Output Module 6ES7-135- 4GB01-0AB0

Add to Wishlist
Add to Wishlist

SIMATIC DP, Electronics module for ET 200S, 2 AO I 15 mm width, +/-20mA; 13 bit+sign, 4..20mA; 13 bit Cycle time less than 1 ms with SF LED (group fault).

Description

Siemens Analog Output Module 6ES7-135- 4GB01-0AB0

Siemens Analog Output Module

General information

Product function

● Isochronous mode No
Supply voltage
Load voltage L+ Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 150 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, max. 2 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog outputs
Number of analog outputs 2
Current output, no-load voltage, max. 18 V
Cycle time (all channels) max. 1.5 ms
Output ranges, current
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for current output two-wire connection Yes
● for current output four-wire connection No
Load impedance (in rated range of output)
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs towards MANA 15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)
● Current, max. 50 mA; DC
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 14 bit; 4 to 20 mA: 13 bit, ±20 mA: 14 bit
Settling time
● for resistive load 0.1 ms
● for capacitive load 0.5 ms
● for inductive load 0.5 ms
Errors/accuracies
Operational error limit in overall temperature range
● Current, relative to output range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to output range, (+/-) 0.3 %
Interrupts/diagnostics/status information
Diagnoses
● Diagnostic information readable Yes
● Wire-break Yes
● Group error Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 7 byte
Diagnostics wire break Disable / enable
Group diagnostics Disable / enable
Response to CPU/master STOP Output current and de-energized/substitute a value/keep last value
Potential separation
Potential separation analog outputs
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g