SCHNEIDER Magnetic Contactor TeSys LC1D32M7
MODEL-LC1D32M7
TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 32 A – 220 V AC coil.
Description
SCHNEIDER Magnetic Contactor TeSys LC1D32M7
Main
Range of product TeSys Deca Product or component type Contactor Device short name LC1D
Contactor application Resistive load Motor control
Utilisation category AC-4 AC-1 AC-3 AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
Complementary
Motor power kW 7.5 kW at 220…230 V AC 50/60 Hz (AC-3) 15 kW at 380…400 V AC 50/60 Hz (AC-3)
15 kW at 415…440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660…690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
7.5 kW at 220…230 V AC 50/60 Hz (AC-3e)
15 kW at 380…400 V AC 50/60 Hz (AC-3e)
15 kW at 415…440 V AC 50/60 Hz (AC-3e)
18.5 kW at 500 V AC 50/60 Hz (AC-3e)
18.5 kW at 660…690 V AC 50/60 Hz (AC-3e)
Motor power hp 2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
20 hp at 460/480 V AC 50/60 Hz for 3 phases motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M2
Protective cover With
SCHNEIDER Magnetic Contactor TeSys LC1D32M7
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit 50 A (at 60 °C) for power circuit
Rated breaking capacity 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
260 A 40 °C – 10 s for power circuit 430 A 40 °C – 1 s for power circuit 60 A 40 °C – 10 min for power circuit 138 A 40 °C – 1 min for power circuit 100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit 63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm – Ith 50 A 50 Hz for power circuit
Power dissipation per pole 2 W AC-3
5 W AC-1
2 W AC-3e
[Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 15 Mcycles
Electrical durability 1.65 Mcycles 32 A AC-3 at Ue <= 440 V
1.4 Mcycles 50 A AC-1 at Ue <= 440 V
1.65 Mcycles 32 A AC-3e at Ue <= 440 V
Control circuit type AC at 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3. 0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8. 1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85. 1.1 Uc (-40…60 °C):operational AC 60 Hz
- 1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA
7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C)