JUMO LOGOSCREEN 700
Operation is made simple with the JUMO LOGOSCREEN 700 paperless recorder’s intuitive, icon-based operation and display approach. It is flexible and available in a variety of forms for process data gathering.
Description
JUMO LOGOSCREEN 700
Highly-scalable paperless recorder
The JUMO LOGOSCREEN 700 paperless recorder is characterized by an intuitive, icon-based operation and visualization concept that makes it easy to operate.Multiple versions of the JUMO LOGOSCREEN 700 are available for process data recording. The high level of scalability allows for flexible adaptation to various customer requirements: from the device version without measurement input (120 process values via interface) through to different device versions with up to 18 measurement inputs (universal analog inputs), 3 analog outputs, 18 digital inputs, 24 individually switchable digital inputs/outputs, and 7 relay outputs. The version with FDA-compliant data recording fulfills all requirements according to 21 CFR Part 11.In order to display the recorded data, the JUMO LOGOSCREEN 700 features various visualizations. In addition, the user can use the setup program to create up to 10 separate process screens – with up to 100 objects per process screen – according to his individual requirements. For batch-based processes, there are up to 5 special batch recordings available, which enable the storage of additional, batch-related information. The extra code, “structured text” allows for the creation of individual measurement and recording applications.
Special features:-
• Intuitive touch operation.
• Up to 3 analog outputs.
• Up to 10 customer-specific process screens.
• Pgrated web server for online visualization as on device.
• Recording of up to 5 batch reports.
• Up to 500 individual texts.
• Limit value monitoring function (120 channels).
• Flow measurement (up to 8 channels).
• Up to 8 counter inputs (max. 12.5 kHz).
• User-specific application using structured text (ST code; extra code).
• Automatic data readout via PCA Communication Software PCC.
• Data recording compliant with FDA 21 CFR Part 11 (extra code).
• Manipulation detection with digital certificate (extra code).
• PC programs for data evaluation and access control.
• AMS2750/CQI-9 (extra code).
• Wide operating temperature range.
Technical data:-
Analog inputs-
General-
Number | Max. 18 (see connection diagram) |
A/D converter | 24 bit delta-sigma |
Sampling rate | Up to 18 channels: 125 ms |
Input filter | Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s |
Galvanic isolation | See “Galvanic isolation” |
Thermocouples
Designation | Type | Standard | ITS | Measuring range | Accuracya |
Fe-CuNi | “L” | DIN 43710 (1985) | IPTS-68 | -200 to +900 °C | ≤ 0.1 % |
Fe-CuNi | “J” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -210 to +1200 °C | ≤ 0.1 % from -100 °C |
Cu-CuNi | “U” | DIN 43710 (1985) | IPTS-68 | -200 to +600 °C | ≤ 0.1 % from -100 °C |
Cu-CuNi | “T” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -270 to +400 °C | ≤ 0.1 % from -150 °C |
NiCr-Ni | “K” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -270 to +1300 °C | ≤ 0.1 % from -80 °C |
NiCr-CuNi | “E” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -270 to +1000 °C | ≤ 0.1 % from -80 °C |
NiCrSi-NiSi | “N” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -270 to +1300 °C | ≤ 0.1 % from -80 °C |
Pt10Rh-Pt | “S” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -50 to +1768 °C | ≤ 0.15 % from 100 °C |
Pt13Rh-Pt | “R” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | -50 to +1768 °C | ≤ 0.15 % from 100 °C |
Pt30Rh-Pt6Rh | “B” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | 0 to 1820 °C | ≤ 0.15 % from 600 °C |
W5Re-W26Re | “C” | DIN EN 60584-1:2014
IEC 60584-1:2013 |
ITS-90 | 0 to 2315 °C | ≤ 0.1 % from 500 °C |
W3Re-W25Re | “D” | ASTM E1751M-15 | ITS-90 | 0 to 2315 °C | ≤ 0.1 % from 500 °C |
W5Re-W20Re | “A1” | GOST R 8.585-2001 | ITS-90 | 0 to 2500 °C | ≤ 0.1 % from 500 °C |
Chromel®-Copel | “L” | GOST R 8.585-2001 | ITS-90 | -200 to +800 °C | ≤ 0.1 % from -80°C |
Chromel®-Alumel® | “K” | GOST R 8.585-2001 | ITS-90 | -270 to +1372 °C | ≤ 0.1 % from -80 °C |
PLII (Platinel® II) | ASTM E1751M-15 | ITS-90 | 0 to 1395 °C | ≤ 0.1 % | |
Ambient temperature influence | ≤ 100 ppm/K | ||||
Cold junction | Internal (Pt100) or external (constant) | ||||
Cold junction accuracy (internal) | Option with 3 analog inputs (order codes 1 and 2): ± 1 K
Option with 6 analog inputs (order code 3): ± 2 K |
||||
Cold junction temperature (external) | -30 to +85 °C (adjustable) | ||||
Base measuring range | -20 to +70 mV |
a Accuracy refers to the measuring range
Analog outputs
Number | Max. 3 (see connection diagram) |
Voltage
Output signal Load resistance |
DC 0 to 10 V
> 500 Ω |
Current
Output signal Load resistance |
DC 0(4) to 20 mA
< 450 Ω |
Accuracy | 0.5 % |
Ambient temperature influence | 150 ppm/K |
JUMO LOGOSCREEN 700
Digital inputs:-
Number | Max. 18 (see connection diagram) |
Input
Level Sampling rate Potential-free contact |
Logic level 0: < 3.5 V; logic level 1: > 10 V
125 ms (max. counting frequency: 4 Hz) RON: < 1 kΩ; ROFF: > 50 kΩ (use of auxiliary voltage 24 V) |
High-speed input
Usable inputs Function Max. counting frequency Mark-to-space ratio Accuracy for flow measurement |
1, 2, 7, 8, 13, 14 (only for analog(HI)/digital option, see connection diagram)
Counts each positive edge of the input signal 12.5 kHz 30 to 70 % (high-pulse ≥ 30 μs, low-pulse ≥ 30 μs) 0.5 % of measured value; ambient temperature influence: 50 ppm/K |
Auxiliary voltage supply
Voltage Current |
DC 24 V +10/-15 %
Max. 50 mA per slot (for analog (HI)/digital option: incl. digital output currents) |
Digital inputs/outputs
Number | Max. 24 (see connection diagram) |
Input or output | Individually configurable as input or output |
Input
Level Sampling rate Potential-free contact |
Logic level 0: < 3.5 V; logic level 1: > 10 V
125 ms (max. counting frequency: 4 Hz) RON: < 1 kΩ; ROFF: > 50 kΩ (use of auxiliary voltage 24 V) |
High-speed input
Usable inputs Function Max. counting frequency Mark-to-space ratio Accuracy for flow measurement |
1, 2 (see connection diagram)
Counts each positive edge of the input signal 12.5 kHz 30 to 70 % (high-pulse ≥ 30 μs, low-pulse ≥ 30 μs) 0.5 % of measured value; ambient temperature influence: 50 ppm/K |
Output
Output signal Current at option – Analog(HI)/digital – Digital |
DC 0/24 V +10/-15 %; galvanically isolated
Max. 40 mA per output, max. 50 mA in total per slot (including auxiliary voltage supply current) Max. 40 mA per output, max. 100 mA in total (including auxiliary voltage supply current) |
Auxiliary voltage supply
Voltage Current at option – Analog(HI)/digital – Digital |
DC 24 V +10/-15 %
Max. 50 mA per slot (including digital outputs current) Max. 100 mA (including digital outputs current) |
RELAY
Number | Max. 7 (see connection diagram) |
Relay (changeover contact)
Switching capacity Contact life |
3 A at AC 230 V or DC 30 V, resistive load
30,000 switching operations at rated load |