LS PLC XBC DR30SU, XBC SU-Type,110/240VAC Input Power

Add to Wishlist
Add to Wishlist

LS Electric XGB Series PLC, XBC Standard SU-Type Unit, 110/240VAC Input Power, 18 24VDC Inputs, 12 Relay Outputs, 2A/Point, 5A/COM, 5 COM, 2 Option slots, Expandable (Max. 254 pts) I/O, Expansion power provision 870mA.

Category:
Tags:

Description

LS PLC XBC DR30SU

General Specifications

Input
Rated Voltage (UL warranty voltage) AC 100 ∽ 240 V
Input voltage range AC85∽ 264V(-15%, +10%)
Inrush current 50APeak or less
Input current 0.5A or less (220V), 1A or less (110V)
Efficiency 65%
Permitted momentary power failure 10ms or less
Power supply status indication LED On when power supply is normal
Rated Output 1.5A @ DC5V; 0.3A @ DC24V
Voltage Ripple DC5V (±2%)
Cable specification 0.75 ∽ 2 mm2
Digital input 0.18 (AWG24) – 1.5 (AWG16)
Digital output 0.18 (AWG24) – 2.0 (AWG14)
Analogue I/O 0.18 (AWG24) – 1.5 (AWG16)
Communication 0.18 (AWG24) – 1.5 (AWG16)
Main power 1.5 (AWG16) – 2.5 (AWG12)
Protective grounding 1.5 (AWG16) – 2.5 (AWG12)
Terminal Strip Torque 3.7 – 5.1 in/lb
Dimensions in. (LxHxD) 5.3 x 3.5 x 2.5″

LS PLC XBC DR30SU

I/O Specifications

DC Inputs
Operation Voltage Range 20.4–28.8VDC (Within Ripple Rate 5% )
Rated Input Voltage 24VDC
Rated Input Current 4mA (Contact Point 0–1: 16mA, 2–7: 10mA)
Input Resistance 5.6kΩ (P00–P07: 2.7kΩ )
On Voltage/On Current 19VDC or Higher/3mA or Higher
Off Voltage/Off Current 6VDC or Less/1mA or Less
Response Time
Off ➔ On / On ➔ Off 1/3/5/10/20/70/100ms (Set by CPU Parameter) Default: 3ms
Insulation Voltage 560VAC rms/3 Cycle (Altitude 2000m)
Insulation Resistance 10MΩ or Higher
Relay Outputs
Rated Load Voltage/Current 24VDC 2A/220VAC 2A, 5A/COM
Min. Load Voltage/Current 5VDC/1mA
Max. Load Voltage 250VAC, 125VDC
Off Leakage Current 0.1mA (220VAC, 60Hz)
Max. On/Off Frequency 3,600 Times/Hour
Response Time
Off ➔ On 10ms or Less
On➔ Off 12ms or Less
Service Life
Mechanical Rated Load Voltage/Current 100,000 Times or More
Electrical 200VAC/1.5A, 240VAC/1A 100,000 Times or More
200VAC/1A, 240VAC/0.5A 100,000 Times or More
24VDC/1A, 100VDC/0.1A 100,000 Times or More

LS PLC XBC DR30SU

Communication Specifications-

Performance Specifications
Program Control Method Fixed Scan Time, Constant Scan
I/O Control Method Scan Synchronous Batch Processing Method (Refresh Method), Directed by Program Instruction
Program Language Ladder Diagram, Instruction List
Processing Speed 94µs /1K boolean
Program Capacity 15k steps
Expansion Capability Expansion Modules and Option Boards (Max. 7 Combined)
Data Area
P P0000–P1023F (16,384 point)
M M0000–M1023F (16,384 point)
K K00000–K4095F (65,536 point)
L L00000–L2047F (32,768 point)
F F000–F1023F (16,384 point)
T 100ms, 10ms, 1ms: T0000–T255 T1023 (1,024 point)(Adjustable by Parameter Setting)
C C000–C1023 (1,024)
S S00.00–S127.99
D D0000–D10239 (10,240 word)
U U00.00–U0A.31 (Analog Data Refresh Area: 352 word)
Z Z000–Z127 (128 word)
R R0000–R10239 (10,240 word)
Total Programs 128
Tasks Available
Initial Task 1
Cyclic Task 8
I/O Task 8
Internal Device Task 8
Operation Mode Run, Stop, Debug
Self-Diagnosis Function Detects Errors of Scan Time, Memory, I/O
Program Ports Mini DIN 6-Pin RS-232C, USB 1 Channel
Back-up Method Latch Area Setting in Basic Parameter
Built-in Functions
PID Control Control by Instruction, Auto-Tuning, PWM Output, Manual Mode, Adjustable Operation Scan Time Setting, Anti-Windup, Delta MV, SV-Ramp Function, Max. 16 Loops
Serial
Protocol Dedicated Protocol, Modbus Protocol, User Defined Protocol
Channel RS-232C 1 port, RS-485 1 port
High Speed Counter
Performance 1 Phase: 100kHz, 2 Channel/20kHz, 6 Channel 2 Phase: 50kHz, 1 Channel/8kHz, 3 Channel
Counter Mode Based on Input Pulse and INC/DEC method – 1 Phase Pulse Input: Addition/Subtraction Counter 2 Phase Pulse Input: Addition/Subtraction Counter 2 Phase Pulse Input: Addition/Subtraction by Pulse Phase Change?(Encoder)
Function Internal/External Preset, Latch Counter, Compare Output, No. of Rotation per Unit Time
Positioning
Control Axis/Method 2 Axis, Position/Speed Control
Control Pulse, Positioning Data: 80 Data/Axis (Operation Step No. 1–80)
Operation End/Keep/Continuous, Single, Repeated Operation
Positioning Method Absolute/Incremental, Address Range: – 2,147,483,648 to 2,147,483,647
Speed Max. 100kpps (Setting Range 1–100,000pps)
Acceleration/Deceleration Trapezoidal Method
Additional Functions Inching Operation, Speed Synchronizing, Position Synchronizing, Linear Interpolation
Pulse Catch 10µs 2 point (P0000–P0001), 50µs 6 point (P0002–P0007)
Input Filtering Time Setting Range 1, 3, 5, 10, 20, 70, 100ms
External Interrupt 10?: 2 Points (P00000–P00001)
50µs : 6 Points (P00002–P00007)
RTC Option Board Required