SIEMENS SIMATIC S7-200 Spare Part 6ES7214-1AD23-0XB0
***Spare part*** SIMATIC S7-200, CPU 224 Compact unit, DC power supply 14 DI DC/10 DO DC, 8/12 KB program./8 KB data, PROFIBUS DP expandable.
Description
SIEMENS SIMATIC S7-200 Spare Part 6ES7214-1AD23-0XB0
TECHNICAL DATA:-
| Supply voltage rated | |
| d value (DC) | |
| ● 24 V DC | Yes |
| Load voltage L+ | |
| ● Rated value (DC) | 24 V |
| ● permissible range, lower limit (DC) | 20.4 V |
| ● permissible range, upper limit (DC) | 28.8 V |
| Input current | |
| inrush current, max. | 12 A; at 28.8 |
| from supply voltage L+, max. | 700 mA; 110 mA to 700 mA, output current for expansion modules (5 V DC)660 mA |
| Encoder supply | |
| 24 V encoder supply | |
| ● 24 V | Yes; permissible range: 15.4 to 28.8 V |
| ● Short-circuit protection | Yes; electronic at 280 mA |
| ● Output current, max. | 280 mA |
| Power loss | |
| Power loss, typ. | 7 W |
| Memory | |
| Number of memory modules (optional) | 1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs, the and other files |
| Work memory | |
| ● integrated (for the program) | 12 kbyte; 8 KB with active run-time edit |
| ● integrated (for data) | 8 kbyte |
| Backup | |
| ● present | Yes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenancefree on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering |
| Battery | |
| Backup battery | |
| ● Backup time, max. | 100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module |
| CPU processing times | |
| for bit operations, max. | 0.22 µs |
| Counters, timers and their retentivity | |
| S7 counter | |
| ● Number | 256 |
| Retentivity | |
| — adjustable | Yes; via high-performance capacitor or battery |
| — lower limit | 1 |
| — upper limit | 256 |
| Counting range | |
| — lower limit | 0 |
| — upper limit | 32 767 |
| S7 times | |
| ● Number | 256 |
| Retentivity | |
| — adjustable | s; via high-performance capacitor or battery |
| — upper limit | 64 |
| Time range | |
| — lower limit | 1 ms |
| — upper limit | 54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to54 min |
| Data areas and their retentivity | |
| Flag | |
| ● Size, max. | 32 byte |
| ● Retentivity available | s; M 0.0 to M 31.7 |
| ● of which retentive with battery | 0 to 255, via high-performance capacitor or battery, adjustable |
| ● of which retentive without battery | 0 to 112 in EEPROM, adjustable |
| Hardware configuration | |
| number of expansion units, max. | 7; Only expansion modules of the S7-22x series can be used. Due to the limited output current, the use of expansion modules may be limited. |
| connectable programming devices/PCs | SIMATIC PG/PC, standard PC |
| Expansion modules | |
| ● Analog inputs/outputs, max. | 35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM) |
| ● Digital inputs/outputs, max. | 168; max. 94 inputs and 74 outputs (CPU + EM) |
| ● AS-Interface inputs/outputs, max. | 62; AS-Interface A/B slaves (CP 243-2) |
| Digital inputs | |
| number of digital inputs | 14 |
| Source/sink inputs | s; optionally, per group |
| input voltage | |
| ● Rated value (DC) | 24 V |
| ● for signal “0” | 0 to 5 V |
| ● for signal “1” | min. 15 V |
| Input current | |
| ● for signal “1”, typ. | 2.5 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
| — parameterizable | Yes; all |
| — at “0” to “1”, min. | 0.2 ms |
| — at “0” to “1”, max. | 12.8 ms |
| for interrupt inputs | |
| — parameterizable | Yes; I 0.0 to I 0.3 |
| for technological functions | |
| — parameterizable | Yes; (E 0.0 to E 1.5) 30 kHz |
| Cable length | |
| ● shielded, max. | 500 m; Standard input: 500 m, high-speed counters: 50 m |
| ● unshielded, max. | 300 m; not for high-speed signals |
| Digital outputs | |
| Number of digital outputs | 10; Transistor |
| Short-circuit protection | o; to be provided externally |
| Limitation of inductive shutdown voltage to | 1 W |
| Switching capacity of the outputs | |
| ● with resistive load, max. | 0.75 A |
| ● on lamp load, max. | 5 W |
| Output voltage | |
| ● for signal “1”, min. | 20 V DC |
| Output current | |
| ● for signal “1” rated value | 750 mA |
| ● for signal “0” residual current, max. | 10 µA |