SIEMENS Analog Output Module 6ES7-135- 4GB01-0AB0
SIMATIC DP, Electronics module for ET 200S, 2 AO I 15 mm width, +/-20mA; 13 bit+sign, 4..20mA; 13 bit Cycle time less than 1 ms with SF LED (group fault).
Description
SIEMENS Analog Output Module 6ES7-135- 4GB01-0AB0
SIEMENS Analog Output Module
| General information | |||
| Product function | |||
| ● Isochronous mode | o | ||
| Supply voltage | |||
| Load voltage L+ | |||
| ● Rated value (DC) | 24 V; From power module | ||
| ● Reverse polarity protection | Yes | ||
| Input current | |||
| from load voltage L+ (without load), max. | 150 mA | ||
| from backplane bus 3.3 V DC, max. | 10 mA | ||
| Power loss | |||
| Power loss, max. | 2 W | ||
| Address area | |||
| Address space per module | |||
| ● Address space per module, max. | 4 byte | ||
| Analog outputs | |||
| Number of analog outputs | 2 | ||
| Current output, no-load voltage, max. | 18 V | ||
| Cycle time (all channels) max. | 1.5 ms | ||
| Output ranges, current | |||
| ● -20 mA to +20 mA | Yes | ||
| ● 4 mA to 20 mA | Yes | ||
| Connection of actuators | |||
| ● for current output two-wire connection | Yes | ||
| ● for current output four-wire connection | No | ||
| Load impedance (in rated range of output) | |||
| ● with current outputs, max. | 500 Ω | ||
| ● with current outputs, inductive load, max. | 1 mH | ||
| Destruction limits against externally applied voltages and currents | |||
| ● Voltages at the outputs towards MANA | 15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20) | ||
| ● Current, max. | 50 mA; DC | ||
| Cable length | |||
| ● shielded, max. | 200 m | ||
| Analog value generation for the outputs | |||
| Integration and conversion time/resolution per channel | |||
| ● Resolution with overrange (bit including sign), max. | 14 bit; 4 to 20 mA: 13 bit, ±20 mA: 14 bit | ||
| Settling time | |||
| ● for resistive load | 0.1 ms | ||
| ● for capacitive load | 0.5 ms | ||
| ● for inductive load | 0.5 ms | ||
| Errors/accuracies | |||
| Operational error limit in overall temperature range | |||
| ● Current, relative to output range, (+/-) | 0.5 % | ||
| Basic error limit (operational limit at 25 °C) | |||
| ● Current, relative to output range, (+/-) | 0.3 % | ||
| Interrupts/diagnostics/status information | |||
| Diagnoses | |||
| ● Diagnostic information readable | Yes | ||
| ● Wire-break | Yes | ||
| ● Group error | Yes | ||
| Diagnostics indication LED | |||
| ● Group error SF (red) | Yes | ||
| Parameter | |||
| Remark | 7 byte | ||
| Diagnostics wire break | Disable / enable | ||
| Group diagnostics | Disable / enable | ||
| Response to CPU/master STOP | Output current and de-energized/substitute a value/keep last value | ||
| Potential separation | |||
| Potential separation analog outputs | |||
| ● between the channels | No | ||
| ● between the channels and backplane bus | Yes | ||
| ● Between the channels and load voltage L+ | Yes | ||
| Isolation | |||
| Isolation tested with | 500 V DC | ||
| Dimensions | |||
| Width | 15 mm | ||
| Height | 81 mm | ||
| Depth | 52 mm | ||
| Weights | |||
| Weight, approx. | 40 g | ||