PULS POWER SUPPLY CT5.121

Add to Wishlist
Add to Wishlist

DIN rail power supplies for 3-phase system 12 V, 8 A

♦ AC 380-480V Wide-range Input.

♦ Input Fuses Already Included.

♦ Requires only Two Legs of a 3-Phase System.

♦ Width only 40mm.

♦ Efficiency up to 85.8%.

♦ Input -Transient Blanking Circuit Included.

♦ Minimal Inrush Current Surge.

♦ Full Power Between -25°C and +60°C.

Description

PULS POWER SUPPLY CT5.121 

CT-Series-3-PHASE, 12V, 8A, 96W.

The Dimension CT-Series are cost-optimized power supplies without compromising quality, reliability, and performance. The CT-Series is part of the DIMENSION power supply family. The most outstanding features of CT5.121 are the high efficiency, electronic inrush current limitation, active input transient filter and wide operational temperature range, small size, and other technological design concepts. The CT-Series includes all the essential basic functions. The CT5.121 utilizes only 2 legs of a 3-phase system which saves wiring and installation costs. Furthermore, this allows a smaller unit without compromising the size of the terminals. Due to the low power consumption, an unbalancing of the individual phases is not expected.

SHORT-FORM DATA-

Output voltage DC 12V Nominal
Adjustment range 12 – 15V Factory setting 12.0V
Output current 8.0 – 6.4A Up to +60°C ambient
6.0 – 4.8A At +70°C ambient
Derate linearly between +60°C and +70°C
Input voltage AC AC 380-480V -15%/+20%
Mains frequency 50-60Hz ±6%
Input current AC 0.64 / 0.56A At 400 / 480Vac
Power factor 0.44 / 0.42 At 400 / 480Vac
AC Inrush current 4 / 4Apk At 400 / 480Vac
Efficiency 85.4 / 85.8% At 400 / 480Vac
Losses 16.4 / 15.9W At 400 / 480Vac
Hold-up time 43 / 63ms At 400 / 480Vac
Temperature range -25°C to +70°C
Size (WxHxD) 40x124x117mm Without DIN rail
Weight 500g

PULS POWER SUPPLY CT5.121

AC-INPUT

The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. Grounding of one phase is allowed except for UL508 applications.

AC input

AC input range

 

Nom.

 

AC 380-480V

323-576Va

576-700Vac

 

 

 

 

 

For maximal 1s (occasional)

 

Allowed voltage L or N to earth

 

Max.

 

500Vac

 

Continuous operation, according to IEC 62477-1

 

Input frequency

 

Nom.

 

50–60Hz

 

±6%

 

Turn-on voltage

 

 

Typ.

Typ.

Typ.

Typ.

 

270Vac

185Vac

215Vac

225Vac

Load independent, steady-state value, see Fig. 3-1

At no load

At 12V, 4A
At 12V, 8A

 

Input current Typ. 0.64A 0.56A At 12V, 8A, see Fig. 3-3
Power factor Typ. 0.44 0.42 At 12V, 8A, see Fig. 3-4
Start-up delay Typ. 75ms 75ms See Fig. 3-2
Rise time Typ. 50ms 50ms At 12V, 8A const. current load, 0mF load

capacitance, see Fig. 3-2

Typ. 85ms 85ms At 12V, 8A const. current load, 8mF load

capacitance, see Fig. 3-2

Turn-on overshoot Max. 100mV 100mV See Fig. 3-2

OUTPUT:-

The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage.The device is designed to supply any kind of loads, including unlimited capacitive and inductive loads.The output is electronically protected against overload, no-load and short-circuits. In case of a protection event,audible noise may occur.

Output voltage Nom. 12V
Adjustment range 12-15V Guaranteed value
Max. 16V This is the maximum output voltage which can occur

at the clockwise end position of the potentiometer

due to tolerances. It is not a guaranteed value which

can be achieved.

Factory setting output voltage Typ. 12.0V ±0.2% at full load, cold unit
Line regulation Max. 10mV Between 323 and 576Vac input voltage change
Load regulation Max. 100mV Between 0 and 8A in “single use” mode, static value
Ripple and noise voltage Max. 100mVpp Bandwidth 20Hz to 20MHz, 50Ohm
Output current Nom. 8.0A At 12V and 60°C ambient temperature
Nom. 6.0A At 12V and 70°C ambient temperature
Nom. 6.4A At 15V and 60°C ambient temperature
Nom. 4.8A At 15V and 70°C ambient temperature
Reduce output current linearly between +60°C and +70°C
Overload behavior Continuous current See Fig. 6-1
Overload/ short-circuit current Max. 15A Continuous current, see Fig. 6-1
Output capacitance Typ. 5 200µF Included inside the power supply
Back-feeding loads Max. 25V The unit is resistant and does not show

malfunctioning when a load feeds back voltage to

the power supply. It does not matter whether the

power supply is on or off. The absorbing energy can

be calculated according to the built-in large sized

output capacitor