| Efficiency |
typ. 92 % (120 V AC) |
| typ. 92.7 % (230 V AC) |
| Output characteristic |
U/I |
| Nominal output voltage |
24 V DC ±1 % |
| Setting range of the output voltage (USet) |
18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) |
20 A |
| POWER BOOST (IBoost) |
26 A (-25 °C … 40 °C permanent, UOUT = 24 V DC ) |
| Static Boost (IStat.Boost) |
26 A |
| Selective Fuse Breaking (ISFB) |
120 A (12 ms) |
| Magnetic circuit breaker tripping |
B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6 |
| Derating |
60 °C … 70 °C (2.5%/K) |
| Feedback voltage resistance |
≤ 35 V DC |
| Protection against overvoltage at the output (OVP) |
≤ 35 V DC |
| Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
| < 2 % (change in load, dynamic 10 % … 90 %) |
| < 0.1 % (change in input voltage ±10 %) |
| Residual ripple |
< 30 mVPP (with nominal values) |
| Short-circuit-proof |
yes |
| Output power |
480 W |
| 624 W |
| Maximum no-load power dissipation |
8 W |
| Power loss nominal load max. |
40 W |
| Rise time |
< 0.1 s (UOUT (10 % … 90 %)) |
| Connection in parallel |
yes, for redundancy and increased capacity |
| Connection in series |
yes |
| Signal: DC OK active |
| Output description |
UOUT > 0.9 x UN: High signal |
| Switching voltage range |
18 V DC … 24 V DC |
| Maximum inrush current |
≤ 20 mA (short-circuit-proof) |
| Continuous load current |
≤ 20 mA |
| Signal: DC OK floating |
| Output description |
Relay contact, UOUT > 0.9 x UN: Contact closed |
| Maximum switching voltage |
30 V AC |
| 24 V DC |
| Maximum inrush current |
0.5 A |
| 1 A |
| Continuous load current |
≤ 1 A |
| Signal: POWER BOOST, active |
| Output description |
IOUT < IN: High signal |
| Switching voltage range |
18 V DC … 24 V DC |
| Output voltage |
+ 24 V DC |
| Maximum inrush current |
20 mA (short-circuit-proof) |
| Continuous load current |
≤ 20 mA |