Nidec – Control Techniques Commander C General Purpose AC drive

Category:

Description

Nidec – Control Techniques Commander C General Purpose AC drive

Control Techniques Commander C Series

Nidec inverter drives

Whatever your application, Commander C is the perfect solution across industries

The Commander C series are simple and compact AC motor speed controllers that meet advanced requirements in a wide range of applications. Their small footprint – among the smallest in their class – makes them ideal for machine builders and OEMs, where size really matters.

 Pumping, ventilating & compressing

  • Improved energy efficiency during periods of low demand
  • On board PLC & PID functionalities make advanced control easy and efficient without the need of an external controller
  • Skip Frequencies allow users to easily avoid equipment resonant frequencies, reducing high vibration levels
  • Supply Loss Ride Through will keep the drive up and running through most power outages
 Conveying

  • Accurate remote speed control with fieldbus communications
  • S-ramp acceleration / deceleration profiling provides smooth speed transitions minimizing machine jerk
  • Overload capacity up to 180% to add stability
  • Avoids early wear and tear of the equipment
 Lifting, hoisting & winching

  • Adjustable mechanical brake sequencing with torque proving function – no need for an external controller
  • Embedded PLC functionality can manage local I/O reducing the need for an external controller
 Access control

  • Smooth motion with enhanced open loop control
  • Small physical size allows the drive to be mounted easily in smaller control cabinets
  • Highly reliable in harsh environments, providing long lasting service
 Processing (mixers, kneaders, crushers, agitators, centrifuges, extruders)

  • Ease of integration to external PLC or other management systems through powerful networking options
  • Conformal coating for enhanced environmental protection
  • Overload capacity up to 180%
  • Highly stable motor control

 

Specifications

Motor Control

C200, C300: Induction Motors 
C300PM: Permanent Magnet Motors

Control Mode

C200 C300 C300 PM
Open loop vector or V / Hz induction motor control  ✓  ✓  ✓
Open loop Rotor Flux Control for induction motors (RFC-A)  ✓  ✓
Sensorless permanent magnet motor control   ✓

Environment

Ambient Operating Temperature Size 1 – 4: -20 °C to 50 °C (-4 °F to 122 °F) @ 3 kHz switching freq. | Operation to 60°C (140°F) with de-rating
Size 5 – 9: -20°C to 40°C (-4°F to 104°F) @ 3 kHz switching freq. | Operation to 55°C (131°F) with de-rating
Cooling Method Forced convection
Humidity 95 % non-condensing at 40 °C (104 °F)
Storage Temperature Size 1 – 4: -40°C to 60°C (-40°F to 140°F) — 24 months Max.
Size 5 – 9: -40°C to 55°C (-40°F to 131°F) — 24 months Max.
Altitude De-rate the continuous output current by 1% for every 100 m (328 ft) above 1000 m (3,280 ft) to a maximum of 3000 m (9,840 ft)
Vibration Tested in accordance with IEC 60068-2-64 and IEC 60068-2-6
Mechanical Shock Tested in accordance with IEC 60068-2-27 and IEC 60068-2-29
Enclosure Rating IP20, NEMA 1 conduit kits available
Electromagnetic Capability IEC/ EN 61800-3 Immunity and Emissions
EN 61000-6-2: Immunity for industrial environments
EN 61000-6-4: Emissions for industrial environmentsM/br> EN 61000-3-2: Harmonic current emissions
An EMC data sheet is available on request
RoHS Complies with the Restriction of Hazardous Substances Directive (2011/65/EU)

AC supply requirements

Voltage 100 V to 120 V ±10 %
200 V to 240 V ±10 %
380 V to 480 V ±10 %
500 V to 575 V ±10 %
500 V to 690 V ±10 %
Phase 1Ø and 3Ø (Model dependent)
Maximum Supply Imbalance 2% negative phase sequence, 3% voltage imbalance between phases
Input Frequency  45 to 66 Hz
Input Displacement Power Factor 0.97

Control

Switching Frequency Size 1 – 4: 0.667, 1, 2, 3, 4, 6, 8 12 & 16 kHz
Size 5 – 9: 2, 3, 4, 6, 8 12 & 16 kHz
Output Frequency Range  0 to 550 Hz
Frequency Accuracy ±0.02% of full scale
Frequency Resolution  0.01 Hz
Analog Input Resolution  Voltage mode: 11 bits (unipolar) Current mode: 11 bits
Braking  Dynamic braking transistor included, requires external resistor

Protection

DC Bus Undervoltage Trip 100 V models: 175 Vdc
200 V models: 175 Vdc
400 V models: 330 Vdc
575 V models: 435 Vdc
690 V models: 435 Vdc
DC Bus Overvoltage Trip Frame sizes 1 – 4:
100 V models: 510 Vdc
200 V models: 510 Vdc
400V models: 870 Vdc
Frame size 5 – 9:
200V models: 415 Vdc
400 V models: 830 Vdc
575 V models: 990 Vdc
690 V models: 1190 Vdc
Drive Overload Trip Programmable: Default settings: 180% for 3s, 150% for 60s
Instantaneous Overcurrent Trip  220% of rated motor current
Phase Loss Trip  DC bus ripple threshold exceeded
Over-temperature Trip  Drive heatsink temperature exceeds 95°C (203°F)
Short Circuit Trip  Protects against output phase-to-phase fault
Ground Fault Trip  Protects against output phase-to-ground fault
Motor Thermal Trip  Electronically protects the motor from overheating due to loading conditions

Data Sheet: PDF

Models Commander C Series:

  • Nidec C200-01100017A10100AB100 (0.25kW / 0.33HP)
  • Nidec C200-01100024A10100AB100 (0.37kW / 0.5HP)
  • Nidec C200-02100042A10100AB100 (0.75kW / 1HP)
  • Nidec C200-02100056A10100AB100 (1.1kW / 1.5HP)
  • Nidec C200-01200017A10100AB100 (0.25kW / 0.33HP)
  • Nidec C200-01200024A10100AB100 (0.37kW / 0.5HP)
  • Nidec C200-01200033A10100AB100 (0.55kW / 0.75HP)
  • Nidec C200-01200042A10100AB100 (0.75kW / 1HP)
  • Nidec C200-02200024A10100AB100 (0.37kW / 0.5HP)
  • Nidec C200-02200033A10100AB100 (0.55kW / 0.75HP)
  • Nidec C200-02200042A10100AB100 (0.75kW / 1HP)
  • Nidec C200-02200056A10100AB100 (1.1kW / 1.5HP)
  • Nidec C200-02200075A10100AB100 (1.5kW / 2HP)
  • Nidec C200-03200100A10100AB100 (2.2kW / 3HP)
  • Nidec C200-04200133A10100AB100 (3kW / 3HP)
  • Nidec C200-04200176A10100AB100 (4kW / 5HP)
  • Nidec C200-05200250A10100AB100 (5.5kW / 7.5HP)
  • Nidec C200-06200330A10100AB100 (7.5kW / 10HP)
  • Nidec C200-06200440A10100AB100 (11kW / 15HP)
  • Nidec C200-07200610A10100AB100 (15kW / 20HP)
  • Nidec C200-07200750A10100AB100 (18.5kW / 25HP)
  • Nidec C200-07200830A10100AB100 (22kW / 30HP)
  • Nidec C200-08201160A10100AB100 (30kW / 40HP)
  • Nidec C200-08201320A10100AB100 (37kW / 50HP)
  • Nidec C200-09201760A10100AB100 (45kW / 60HP)
  • Nidec C200-09202190A10100AB100 (55kW / 75HP)
  • Nidec C200-09201760E10100AB100 (45kW / 60HP)
  • Nidec C200-09202190E10100AB100 (55kW / 75HP)
  • Nidec C200-02400013A10100AB100 (0.37kW / 0.5HP)
  • Nidec C200-02400018A10100AB100 (0.55kW / 0.75HP)
  • Nidec C200-02400023A10100AB100 (0.75kW / 1HP)
  • Nidec C200-02400032A10100AB100 (1.1kW / 1.5HP)
  • Nidec C200-02400041A10100AB100 (1.5kW / 2HP)
  • Nidec C200-03400056A10100AB100 (2.2kW / 3HP)
  • Nidec C200-03400073A10100AB100 (3kW / 3HP)
  • Nidec C200-03400094A10100AB100 (4kW / 5HP)
  • Nidec C200-04400135A10100AB100 (5.5kW / 7.5HP)
  • Nidec C200-04400170A10100AB100 (7.5kW / 10HP)
  • Nidec C200-05500030A10100AB100 (1.5kW / 2HP)
  • Nidec C200-05500040A10100AB100 (2.2kW / 3HP)
  • Nidec C200-05500069A10100AB100 (4kW / 5HP)
  • Nidec C200-06500100A10100AB100 (5.5kW / 7.5HP)
  • Nidec C200-06500150A10100AB100 (7.5kW / 10HP)
  • Nidec C200-06500190A10100AB100 (11kW / 15HP)
  • Nidec C200-06500230A10100AB100 (15kW / 20HP)
  • Nidec C200-06500290A10100AB100 (18.5kW / 25HP)
  • Nidec C200-06500350A10100AB100 (22kW / 30HP)
  • Nidec C200-07500440A10100AB100 (30kW / 40HP)
  • Nidec C200-07500550A10100AB100 (37kW / 50HP)
  • Nidec C200-08500630A10100AB100 (45kW / 60HP)
  • Nidec C200-08500860A10100AB100 (55kW / 75HP)
  • Nidec C200-09501040A10100AB100 (75kW / 100HP)
  • Nidec C200-09501310A10100AB100 (90kW / 125HP)
  • Nidec C200-09501040E10100AB100 (75kW / 100HP)
  • Nidec C200-09501310E10100AB100 (90kW / 125HP)
  • Nidec C200-07600190A10100AB100 (15kW / 20HP)
  • Nidec C200-07600240A10100AB100 (18.5kW / 25HP)
  • Nidec C200-07600290A10100AB100 (22kW / 30HP)
  • Nidec C200-07600380A10100AB100 (30kW / 40HP)
  • Nidec C200-07600440A10100AB100 (37kW / 50HP)
  • Nidec C200-07600540A10100AB100 (45kW / 60HP)