SIEMENS Analog Output Module 6ES7135-4GB01-0AB0
SIMATIC DP, Electronics module for ET 200S, 2 AO I 15 mm width, +/-20mA; 13 bit+sign, 4..20mA; 13 bit Cycle time less than 1 ms with SF LED (group fault).
Description
SIEMENS Analog Output Module 6ES7135-4GB01-0AB0
SIEMENS Analog Output Module
DATA SHEET:-
| General information | ||
| Product function | ||
| ● Isochronous mode | No | |
| Supply voltage | ||
| Load voltage L+ | ||
| ● Rated value (DC) | 24 V; From power module | |
| ● Reverse polarity protection | Yes | |
| Input current | ||
| from load voltage L+ (without load), max. | 150 mA | |
| from backplane bus 3.3 V DC, max. | 10 mA | |
| Power loss | ||
| Power loss, max. | 2 W | |
| Address area | ||
| Address space per module | ||
| ● Address space per module, max. | 4 byte | |
| Analog outputs | ||
| Number of analog outputs | 2 | |
| Current output, no-load voltage, max. | 18 V | |
| Cycle time (all channels) max. | 1.5 ms | |
| Output ranges, current | ||
| ● -20 mA to +20 mA | Yes | |
| ● 4 mA to 20 mA | Yes | |
| Connection of actuators | ||
| ● for current output two-wire connection | Yes | |
| ● for current output four-wire connection | No | |
| Load impedance (in rated range of output) | ||
| ● with current outputs, max. | 500 Ω | |
| ● with current outputs, inductive load, max. | 1 mH | |
| Destruction limits against externally applied voltages and currents | ||
| ● voltage / between the analog outputs and reference
potential of the analog measuring circuit / as destruction limit for externally applied voltage / maximum permissible |
15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20) | |
| ● current / at the analog outputs / as destruction limit for
externally applied voltage / maximum permissible |
50 mA; DC | |
| Cable length | ||
| ● shielded, max. | 200 m | |
| Analog value generation for the outputs | ||
| Integration and conversion time/resolution per channel | ||
| ● Resolution with overrange (bit including sign), max. | 14 bit; 4 to 20 mA: 13 bit, ±20 mA: 14 bit | |
| Settling time | ||
| ● for resistive load | 0.1 ms | |
| ● for capacitive load | 0.5 ms | |
| ● for inductive load | 0.5 ms | |
| Errors/accuracies | ||
| Operational error limit in overall temperature range | ||
| ● Current, relative to output range, (+/-) | 0.5 % | |
| Basic error limit (operational limit at 25 °C) | ||
| ● Current, relative to output range, (+/-) | 0.3 % | |
| Interrupts/diagnostics/status information | ||
| Diagnoses | ||
| ● Diagnostic information readable | Yes | |
| ● Wire-break | Yes | |
| ● Group error | Yes | |
| Diagnostics indication LED | ||
| ● Group error SF (red) | Yes | |
| Parameter | ||
| Remark | 7 byte | |
| Diagnostics wire break | Disable / enable | |
| Group diagnostics | Disable / enable | |
| Response to CPU/master STOP | Output current and de-energized/substitute a value/keep last value | |
| Potential separation | ||
| Potential separation analog outputs | ||
| ● between the channels | No | |
| ● between the channels and backplane bus | Yes | |
| ● Between the channels and load voltage L+ | Yes | |
| Isolation | ||
| Isolation tested with | 500 V DC | |
| Dimensions | ||
| Width | 15 mm | |
| Height | 81 mm | |
| Depth | 52 mm | |
| Weights | ||
| Weight, approx. | 40 g | |