Siemens DIN Rail Power Supply Sitop -6EP1333-2BA20-5A
SITOP PSU100S/1AC/24VDC/5A
SITOP PSU100S 24 V/5 A Stabilized power supply input: 120/230 V AC, output: 24 V DC/5 A *Ex approval no longer available.
Description
Siemens DIN Rail Power Supply Sitop-6EP1333-2BA20-5A
DIN Rail Power Supply
| Input | |
| type of the power supply network | 1-phase AC |
| supply voltage at AC | |
| ● initial value | Automatic range selection |
| supply voltage | |
| ● 1 at AC rated value | 120 V |
| ● 2 at AC rated value | 230 V |
| input voltage | |
| ● 1 at AC | 85 … 132 V |
| ● 2 at AC | 170 … 264 V |
| design of input wide range input | No |
| overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
| operating condition of the mains buffering | at Vin = 93/187 V |
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms |
| operating condition of the mains buffering | at Vin = 93/187 V |
| line frequency | |
| ● 1 rated value | 50 Hz |
| ● 2 rated value | 60 Hz |
| line frequency | 47 … 63 Hz |
| input current | |
| ● at rated input voltage 120 V | 2.34 A |
| ● at rated input voltage 230 V | 1.36 A |
| current limitation of inrush current at 25 °C maximum | 40 A |
| I2t value maximum | 1 A²·s |
| fuse protection type | T 3,15 A/250 V (not accessible) |
| ● in the feeder | Recommended miniature circuit breaker: from 6 A characteristic C |
| Output | |
| voltage curve at output | Controlled, isolated DC voltage |
| output voltage at DC rated value | 24 V |
| output voltage | |
| ● at output 1 at DC rated value | 24 V |
| relative overall tolerance of the voltage | 3 % |
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % |
| ● on slow fluctuation of ohm loading | 1 % |
| residual ripple | |
| ● maximum | 150 mV |
| ● typical | 30 mV |
| voltage peak | |
| ● maximum | 240 mV |
| ● typical | 140 mV |
| adjustable output voltage | 22.8 … 28 V |
| product function output voltage adjustable | Yes |
| type of output voltage setting | via potentiometer |
| display version for normal operation | Green LED for 24 V OK |
| type of signal at output | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK” |
| behavior of the output voltage when switching on | Overshoot of Vout < 3 % |
| response delay maximum | 0.3 s |
| voltage increase time of the output voltage | |
| ● typical | 15 ms |
| output current | |
| ● rated value | 5 A |
| ● rated range | 0 … 6 A; 6 A up to +45°C; +60 … +70 °C: Derating 1.6%/K |
| supplied active power typical | 144 W |
| short-term overload current | |
| ● on short-circuiting during the start-up typical | 18 A |
| ● at short-circuit during operation typical | 18 A |
| duration of overloading capability for excess current | |
| ● on short-circuiting during the start-up | 800 ms |
| ● at short-circuit during operation | 800 ms |
| product feature | |
| ● bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing
the power |
2 |
| Efficiency | |
| efficiency in percent | 88 % |
| power loss [W] | |
| ● at rated output voltage for rated value of the output
current typical |
16 W |
| Closed-loop control | |
| relative control precision of the output voltage with rapid
fluctuation of the input voltage by +/- 15% typical |
0.3 % |
| relative control precision of the output voltage at load step of
resistive load 10/90/10 % typical |
3 % |
| setting time | |
| ● load step 10 to 90% typical | 1 ms |
| ● load step 90 to 10% typical | 1 ms |
| Protection and monitoring | |
| design of the overvoltage protection | protection against overvoltage in case of internal fault Vout < 33 V |
| response value current limitation | 6 … 7.1 A |
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Constant current characteristic |
| enduring short circuit current RMS value | |
| ● typical | 7.1 A |
| overcurrent overload capability in normal operation | overload capability 150 % Iout rated up to 5 s/min |
| display version for overload and short circuit | – |
| Safety | |
| galvanic isolation between input and output | Yes |
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
| operating resource protection class | Class I |
| leakage current | |
| ● maximum | 3.5 mA |
| ● typical | 0.4 mA |
| protection class IP | IP20 |
| Approvals | |
| certificate of suitability | |
| ● CE marking | Yes |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1) |
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1) |