STAHL Safety Temperature Monitor & Limiter Series 8146/5
- When a user-defined temperature is reached or dropped below, the device disconnects; a switching capacity of up to 25 A.
- In the event of a leak in the liquid-filled measurement system, there will be a permanent disconnect.
-
Series 8146 E ex e enclosures are available in standardized forms. On request, customized solutions are available.
Description
STAHL Safety Temperature Monitor & Limiter Series 8146/5
STAHL safety temperature monitors and limiters perform various tasks: They disconnect the system after an adjustable limit value is exceeded, whereby limiters remain disconnected, while controllers switch back on again when the permissible temperature is reached. Both switch off in the event of a leak in the system. The set value can be seen from the outside through the inspection window.
Selection Table | |||
Product Description Safety temperature limiter.
Cable glands and entries 1 x M20 Ø 4 … 13 mm. |
|||
Measuring range | Product Type | Art. No. | Weightkg |
Safety temperature limiter: 0 to 120 °C | 8146/ 5041- STB25A/+0…+120°C | 136011 n | 1.000 |
Product Description Safety temperature monitor
Cable glands and entries 1 x M20 Ø 4 … 13 mm |
|||
Measuring range | Product Type | Art. No. | Weightkg |
Safety temperature monitor: -20 to 50 °C | 8146/ 5041- STW25A/-20- +50°C | 136043 n | 1.000 |
Safety temperature monitor: 0 to 190 °C | 8146/ 5041- STW25A/ 0- +190°C | 136081 n | 1.000 |
Product Description Safety temperature monitor And safety temperature limiter
Cable glands and entries 2 x M20 Ø 4 to 13 mm |
|||
Measuring range | Product Type | Art. No. | Weightkg |
Safety temperature limiter: 0 to 190 °CSafety temperature monitor: 0 to 120 °C | 8146/ 5051- STW25A+STB25A | 269562 n | 1.440 |
Technical Data | |
Electrical Data:- | |
Rated operational voltage AC | 230 V |
Rated operational current | 25 A (T6) |
Notes | Change-over contact, specific to safety temperature monitors and limiters in acc. with EN 14597:
– the power can be switched via contact paths 1-2 – the contact path 1-4 is used for signaling purposes |
Output | |
Max. output AC load condition | 1 to 2 230 VAC1 / 25 A
1 to 4 230 VAC1 / 2 A |
Ambient Conditions | |
Ambient temperature | -60 °C … +40 °C |
Mechanical Data:- | |
Degree of protection (IP) | IP66 |
Enclosure material polyester | r resin, Glass fibre reinforced |
Capillary tube length | 1 m |
Capillary tube diameter | 1.5 mm |
Contacts | 1 change- over contact |
Components:- | |
Cable entry material | Polyamide, black |