Phoenix Contact Power Supply QUINT-PS/1AC/24DC/20

Add to Wishlist
Add to Wishlist

SFB Technology (Selective Fuse Breaking), Screw connection, DIN rail mounting, Primary-switched Power Supply Unit by QUINT POWER, Input: 1-Phase, Output: 24 DC 20 A.

Description

Phoenix Contact Power Supply QUINT-PS/1AC/24DC/20

Phoenix Contact Power Supply

TECHNICAL DATA:-

INPUT DATA-
AC operation
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Derating IStat. Boost < 100 V AC (1 %/V)
Input voltage range AC 85 V AC … 264 V AC
Input voltage range DC 90 V DC … 350 V DC
Electric strength, max. 300 V AC
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current < 20 A
Inrush current integral (I2t) < 3.2 A2s
Inrush current limitation 20 A
AC frequency range 45 Hz … 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 32 ms (120 V AC)
> 32 ms (230 V AC)
Current consumption 7 A (100 V AC)
5.8 A (120 V AC)
3 A (230 V AC)
3.1 A (240 V AC)
Nominal power consumption 569 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.89
Typical response time < 0.6 s
Input fuse 12 A (slow-blow, internal)
Permissible backup fuse B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 10 A … 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
DC operation
Nominal input voltage range 110 V DC … 250 V DC
Input voltage range 110 V DC … 250 V DC -18 % … +40 %
Derating IStat. Boost < 110 V DC (1 %/V)
Current consumption 6.3 A (110 V DC)
2.8 A (220 V DC)

OUTPUT DATA

Efficiency typ. 92 % (120 V AC)
typ. 92.7 % (230 V AC)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 20 A
POWER BOOST (IBoost) 26 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Static Boost (IStat.Boost) 26 A
Selective Fuse Breaking (ISFB) 120 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 35 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 30 mVPP (with nominal values)
Short-circuit-proof yes
Output power 480 W
624 W
Maximum no-load power dissipation 8 W
Power loss nominal load max. 40 W
Rise time < 0.1 s (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current ≤ 20 mA (short-circuit-proof)
Continuous load current ≤ 20 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage 30 V AC
24 V DC
Maximum inrush current 0.5 A
1 A
Continuous load current ≤ 1 A
Signal: POWER BOOST, active
Output description IOUT < IN: High signal
Switching voltage range 18 V DC … 24 V DC
Output voltage + 24 V DC
Maximum inrush current 20 mA (short-circuit-proof)
Continuous load current ≤ 20 mA