Phoenix Contact Power Supply QUINT-PS/1AC/24DC/20
Add to Wishlist
Add to Wishlist
SFB Technology (Selective Fuse Breaking), Screw connection, DIN rail mounting, Primary-switched Power Supply Unit by QUINT POWER, Input: 1-Phase, Output: 24 V DC / 20 A.
Description
Phoenix Contact Power Supply QUINT-PS/1AC/24DC/20
Phoenix Contact Power Supply
TECHNICAL DATA:-
INPUT DATA-
AC operation |
Nominal input voltage range | 100 V AC … 240 V AC |
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
Derating IStat. Boost | < 100 V AC (1 %/V) |
Input voltage range AC | 85 V AC … 264 V AC |
Input voltage range DC | 90 V DC … 350 V DC |
Electric strength, max. | 300 V AC |
Typical national grid voltage | 120 V AC |
230 V AC | |
Voltage type of supply voltage | AC |
Inrush current | < 20 A |
Inrush current integral (I2t) | < 3.2 A2s |
Inrush current limitation | 20 A |
AC frequency range | 45 Hz … 65 Hz |
Frequency range DC | 0 Hz |
Mains buffering time | > 32 ms (120 V AC) |
> 32 ms (230 V AC) | |
Current consumption | 7 A (100 V AC) |
5.8 A (120 V AC) | |
3 A (230 V AC) | |
3.1 A (240 V AC) | |
Nominal power consumption | 569 VA |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | 0.89 |
Typical response time | < 0.6 s |
Input fuse | 12 A (slow-blow, internal) |
Permissible backup fuse | B10 B16 AC: |
Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
Recommended breaker for input protection | 10 A … 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA |
DC operation | |
Nominal input voltage range | 110 V DC … 250 V DC |
Input voltage range | 110 V DC … 250 V DC -18 % … +40 % |
Derating IStat. Boost | < 110 V DC (1 %/V) |
Current consumption | 6.3 A (110 V DC) |
2.8 A (220 V DC) |
OUTPUT DATA
Efficiency | typ. 92 % (120 V AC) |
typ. 92.7 % (230 V AC) | |
Output characteristic | U/I |
Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (USet) | 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 20 A |
POWER BOOST (IBoost) | 26 A (-25 °C … 40 °C permanent, UOUT = 24 V DC ) |
Static Boost (IStat.Boost) | 26 A |
Selective Fuse Breaking (ISFB) | 120 A (12 ms) |
Magnetic circuit breaker tripping | B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6 |
Derating | 60 °C … 70 °C (2.5%/K) |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (change in load, dynamic 10 % … 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 30 mVPP (with nominal values) |
Short-circuit-proof | yes |
Output power | 480 W |
624 W | |
Maximum no-load power dissipation | 8 W |
Power loss nominal load max. | 40 W |
Rise time | < 0.1 s (UOUT (10 % … 90 %)) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal: DC OK active | |
Output description | UOUT > 0.9 x UN: High signal |
Switching voltage range | 18 V DC … 24 V DC |
Maximum inrush current | ≤ 20 mA (short-circuit-proof) |
Continuous load current | ≤ 20 mA |
Signal: DC OK floating | |
Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
Maximum switching voltage | 30 V AC |
24 V DC | |
Maximum inrush current | 0.5 A |
1 A | |
Continuous load current | ≤ 1 A |
Signal: POWER BOOST, active | |
Output description | IOUT < IN: High signal |
Switching voltage range | 18 V DC … 24 V DC |
Output voltage | + 24 V DC |
Maximum inrush current | 20 mA (short-circuit-proof) |
Continuous load current | ≤ 20 mA |