Fluke 1623-2 GEO Earth Ground Resistance Meter

  • A unique earth ground tester that performs fast, accurate testing with and without stakes
  • Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
  • Performs selective earth ground rod testing (one clamp + stakes)
  • Performs stakeless earth ground rod testing (two clamps)
  • Features IP56 rating for outdoor use

Description

Fluke 1623-2 GEO Earth Ground Resistance Meter

Fluke Earth Ground Resistance Meter

Model#: Fluke 1623-2

Earth ground testers

It is critical for facilities to have grounded electrical systems, so that in the event of a lightning strike or utility overvoltage, current will find a safe path to earth. To ensure a reliable connection to earth, the International Electrical Testing Association specifies ground electrode testing every three years.

Fluke’s family of electrical earth ground testers have been built to address the entire spectrum of ground testing methods from the basic to the most advanced. Our testers have been designed to be accurate, safe and easy to use. We provide quick and precise resistance measurements through several test methods: 3- and 4-pole Fall-of-Potential testingselective measurement testingstakeless testing and 2-pole testing.

Fluke 1623-2 Earth Ground Tester performs all four ground tests quickly and accurately.

The Fluke 1623-2 earth ground tester measures earth ground loop resistances using only clamps, only stakes, or one clamp and stakes. With the stakeless test method, the Fluke 1623-2 is able to measure earth ground loop resistances for multi-grounded systems using only current clamps. This technique eliminates the dangerous, and time consuming job of disconnecting parallel grounds, and finding suitable locations for auxiliary ground stakes. You can use it to perform earth ground tests in places you’ve not considered before, such as inside buildings, on power pylons, or anywhere you don’t have access to soil.

 

Specifications: Fluke 1623-2 GEO Earth Ground Resistance Meter

General Specifications
Display: 1999 digit LCD Display with special symbols, digit height 25 mm, fluorescent backlight
User interface Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, water and dust resistant Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Memory Internal memory storage up to 1500 records accessible via USB port
Temperature Range
Operating temperature -10°C to 50°C (14°F to 122°F)
Storage temperature -30°C to 60°C (-22°F to 140°F)
Temperature coefficient ±0.1% of reading/°C < 18°C > 28°C
Intrinsic error Refers to the reference temperature range and is guaranteed for 1 year
Operating error Refers to the operating temperature range and is guaranteed for 1 year
Climatic class C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
Protective type IP56 for case, IP40 for battery door according to EN60529
Safety Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2
EMC (emission immunity) IEC61326-1: Portable
Quality system Developed, designed and manufactured according to DIN ISO 9001
External voltage V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
V ext rejection > 120 dB (162⁄3, 50, 60, 400 Hz)
Measuring time Typical 6 seconds
Max. overload 250 V rms (pertains to misuse)
Auxiliary power 6 x 1.5 V Alkaline (type AA LR6)
Battery life span Typical > 3,000 measurements
Dimensions (W x H x D) 250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
Weight 1.1 kg (2.43 lb) including batteries
7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
Switch position RA 3-pole
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
Switch position RA 4-pole
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS + RES) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch position RA 3-pole with clamp
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch position RA 4-pole with clamp
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltage Vm = 48 V AC
Short-circuit current > 50 mA
Measure frequency 128 Hz
Probe resistance (RS) Max 100 kΩ
Auxiliary earth electrode resistance (RH) Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
Stakeless Ground Loop Measurement (2 Clamps)
Switch position RA 4-pole 2 clamps
Resolution 0.001 Ω to 10 Ω
Measuring range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating error ±(10% rdg + 5 d)
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
Measuring voltage Vm = 48 V AC
Measure frequency 128 Hz
Noise current (IEXT) Max. IEXT = 10 A (AC) (RA < 20 Ω)
Max. IEXT = 2 A (AC) (RA > 20 Ω)
Automatic range selection.
The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.

 

Datasheet: PDF

 

Why Choose Voltec Engineering Limited?

At Voltec Engineering Limited, we are proud to be the authorized distributor of Leuze Electronic in Bangladesh. As a trusted Leuze sensor supplier in Bangladesh and leading industrial automation supplier Bangladesh, we deliver best quality proximity sensors, photoelectric sensors, diffuse sensors,Leuze retroreflective sensor supplier in Bangladesh, through-beam sensors supplier in bangladesh, fork Sensors, barcode scanners, safety light curtains, inductive sensors, capacitive sensors supplier in bangladesh, optical sensors, Leuze Fork Sensor Supplier In Bangladesh and machine safety products.We ensure top-quality Leuze sensors in Bangladesh, backed by exceptional technical support and a wide range of automation solutions in Bangladesh. Our experienced team provides guidance on sensor selection, PLC programming, HMI integration, VFD and inverter panels, and automation project design to meet your requirements. With ready stock and fast deliveryVoltec Engineering Limited is your reliable Leuze distributor Bangladesh.

In addition to Leuze, we also supply a wide range of industrial products from other global brands such as Siemens, Omron, ABB, Allen Bradley, Delta, Yaskawa Schneider, Mitsubishi, and many more — ensuring complete automation, sensing, and electrical solutions under one roof. For assistance or to place an order, don’t hesitate to contact usVoltec Engineering Limited is here to support you with Leuze Electronic Bangladesh, Sick photo sensor Bangladesh, Pepperl+Fuchs sensor Bangladesh, IFM sensor Bangladesh, Balluff Sensor Bangladesh, Fluke Instruments Bangladesh, Fluke Thermal Imager, Fluke Multimeter, Fluke Clamp Meter, Fluke Earth Ground Meter, Fluke Battery Analyzer, Fluke IR Thermometers, Fluke Laser Alignment, Fluke, Fluke Vibration Meter, Fluke Vibration Tester, Autonics Temperature Controller, Siemens Inverter, 0.75kw Inverter Siemens, Siemens 0.75kw VFD, Selec Timer Bangladesh, Omron PLC Bangladesh, ABB automation spare parts Bangladesh, Siemens PLC supplier in Bangladesh, Selec temperature controller supplier in bd, Schneider HMI supplier Bangladesh, Delta VFD supplier Bangladesh, Mitsubishi Inverter Bangladesh, Yaskawa inverter supplier Bangladesh, Keyence industrial sensors Bangladesh — ensuring efficiency, precision, and reliability in your operations.